Inspections for the day of: Friday, February 6, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-02796 Final2/6/20152/6/20152/6/2015 3:42:29 PMPPART
Phone #: ###-#### Inspection requested via web by Thomas Jenkins 210.8- Mech rm GFCI protect receptacle located with in 6' of sink.
110.24- Available fault current shall be posted on service.
406.5- Receptacle outlets shall be secured in place. Outdoor by east door.

No card posted. Temporary final ok
ELE07-02082 ELE-Aging Inspection2/6/20152/6/20152/6/2015 3:37:27 PM DONE
Still under construction
ELE15-00321 Final2/6/20152/6/20152/6/2015 3:06:37 PMPPASS
###-#### Final ok
ELE15-00321 Permanent Service2/6/20152/6/20152/6/2015 3:06:21 PMPPASS
###-#### Underground shallow due to rock hit and installed in rigid conduit. p/s u/g n ok
ELE14-02213 Electrical Rough-In2/6/20152/6/20152/6/2015 2:55:43 PMPPASS
Mike Phone #: ###-#### Grid in exam rooms and exam corridors rough in ok cover
ELE15-00320 Conference2/6/20152/6/20152/6/2015 12:54:41 PMPDONE
Discussed the discovery of illegal wiring through out entire house.
Boise Municiplal Code
Section 4-05-32 CODE VIOLATION NOT TO BE RETAINED
When altering a pre-existing electrical wire, equipment, apparatus or fixture, or adding any new
wiring, the existing electrical wiring in close proximity shall be in accordance with the present
code.
(6338, Added, 08/03/2004)
Section 4-05-23 UNLAWFUL TO CONCEAL
It shall be unlawful for any person, to cover up or in any way conceal any electrical wiring,
cables, conduits or other equipment until the same has been inspected and approved by an
Electrical Inspector.
(6338, Added, 08/03/2004)
Section 4-05-29 RESPONSIBILITY
Regardless of any approval issued by the City of Boise, the owner or authorized agent shall have
ultimate responsibility to comply with all articles of this Code. Boise City officials,
employees or agent, shall not be held liable by reason of the issuance of any permit, inspection or
by reason of any final inspection approval issued by the Electrical Inspector.
(6338, Added, 08/03/2004
ELE15-00321 Permanent Service2/5/20152/6/20152/6/2015 11:42:04 AMAFAIL
Phone #: ###-#### Inspection requested via web by Don Conley 250.24- Premisis wiring shall have a grounding electode system conductor connected to the grounded conductor at each service.
250.92-Standard locknuts and bushings shall not be only means of bonding metal raceway on supply side of service.
ELE15-00203 Electrical Rough-In2/5/20152/6/20152/6/2015 10:30:30 AMAPASS
Underground cover inspection. North West corner of the Edwards complex. Danny is the on site contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Under ground for sign located on N.W. corner near chuck-a-rama rough in ok cover
ELE15-00271 Electrical Rough-In2/5/20152/6/20152/6/2015 9:39:06 AMAPART
Von. Pony deli wall ; wall on the right side of the pony wall. New deli department. Phone #: ###-#### Inspection requested via web by Sean DeLacy Called contractor to inform of broken PVC near back corner where fllor opened up for refrigeration lines. Wall in back corner of deli rough in ok cover
ELE15-00272 Final2/5/20152/6/20152/6/2015 9:08:10 AMAPASS
garage door code: 3655
front door code: 25579 Phone #: ###-#### Inspection requested via web by Richard Gratiot Final ok
ELE14-02186 Conference2/6/20152/6/20152/6/2015 8:49:26 AMPDONE
Per phone conversation. Owner called to ask if addition of ground rods to grounding electode system location in crawl space was an acceptable location. Flooring removed to allow access for vertical installation of ground rods. told owner if rods were able to be installed vertically location is acceptable.
ELE15-00284 Temporary Service2/5/20152/6/20152/6/2015 8:45:45 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE15-00317 Final2/5/20152/6/20152/5/2015 3:52:38 PMACANC
Power off for more than 1 year.

Lock Box - OCN

Front Door - 35421 Phone #: ###-#### >> Inspection requested via web by steve ragan Inspection cancelled from web by: steve ragan