Inspections for the day of: Friday, February 6, 2015.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBill VanDegrift
TitlePLM-INSPECTOR
Phone #794-9372
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC15-00541 Final2/5/20152/6/20152/6/2015 4:19:51 PMPPASS
Installer Jason ###-#### Phone #: ###-#### Inspection requested via web by Dustin Rich 20# flue test ok
MEC15-00541 Pressure Test2/5/20152/6/20152/6/2015 4:19:22 PMPPASS
Gas piper Miguel ###-#### Phone #: ###-#### Inspection requested via web by Dustin Rich 20# test ok
MEC14-04684 Final2/6/20152/6/20152/6/2015 4:18:56 PMPNR
Installed a furnace. need to pressure test the vent, and final on the furnace install.

Can you call about thirty minutes before heading over? Phone #: ###-#### Inspection requested via web by Nat Golden flue test wouldn't hold then equipment failure
PLM15-00347 Water and/or Sewer2/6/20152/6/20152/6/2015 3:24:19 PMPPART
late afternoon please like 3pm Phone #: ###-#### Inspection requested via web by Scott Wickstrom water sevice ok just needs PVB tested, it's out back
MEC15-00306 Rough-in2/5/20152/6/20152/6/2015 1:06:14 PMPPASS
Phone #: ###-#### Inspection requested via web by Chris Wieboldt
MEC15-00307 Rough-in2/5/20152/6/20152/6/2015 1:05:56 PMPPASS
Phone #: ###-#### Inspection requested via web by Chris Wieboldt
MEC14-04690 Final2/5/20152/6/20152/6/2015 12:09:10 PMAPASS
###-#### Jim gas pipe final ok
MEC14-04690 Pressure Test2/5/20152/6/20152/6/2015 12:08:09 PMAPASS
###-#### Jim. 20# test ok
PLM15-00298 Plumbing Rough-in2/5/20152/6/20152/6/2015 9:55:22 AMAPART
Juan Phone #: ###-#### dwv test ok roof drains need to be piped inside to crawlspace then to fromt of the building.
MEC15-00551 Rough-in2/5/20152/6/20152/6/2015 9:03:36 AMAFAIL
Stan ###-####/ Cover inspection Phone #: ###-#### Inspection requested via web by Crystal Grant exhaust duct from restrooms will be smashed when sheetrock is installed provide additional space in ceiling or transtions fittings to go under the red iron. gave correction notice to super in trailor.
MEC12-03085 Mec-Aging Inspection2/6/20152/6/20152/6/2015 8:01:56 AM FAIL
expire permit
MEC12-03085 DOC - Permit Expired2/6/20152/6/20152/6/2015 8:01:31 AMPPASS
expire permit
MEC12-03092 Mec-Aging Inspection2/6/20152/6/20152/6/2015 8:00:31 AM FAIL
expire permit
MEC12-03092 DOC - Permit Expired2/6/20152/6/20152/6/2015 8:00:06 AMPPASS
expire permit
MEC12-03093 Mec-Aging Inspection2/6/20152/6/20152/6/2015 7:59:20 AM FAIL
expire permit
MEC12-03093 DOC - Permit Expired2/6/20152/6/20152/6/2015 7:58:52 AMPCANC
expire permit
MEC13-03783 Mec-Aging Inspection2/6/20152/6/20152/6/2015 7:57:55 AM PASS
expire permit
MEC13-03783 DOC - Permit Expired2/6/20152/6/20152/6/2015 7:57:34 AMPPASS
expire permit