ELE14-03237
| Final | 2/6/2015 | 2/6/2015 | 2/6/2015 2:42:25 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov corrections made ?Final OK
|
ELE15-00255
| Electrical Rough-In | 2/6/2015 | 2/6/2015 | 2/6/2015 2:21:30 PM | P | PASS |
|
|
Remodel the basement Phone #: ###-#### Inspection requested via web by Neal Rumsey basement ri ok to cover
|
ELE15-00300
| Permanent Service | 2/4/2015 | 2/6/2015 | 2/6/2015 1:27:11 PM | P | PASS |
|
|
Please make this inspection for later in the afternoon. Phone #: ###-#### Inspection requested via web by Thomas Jenkins PS, OH, N, OK
|
ELE14-02714
| Final | 2/5/2015 | 2/6/2015 | 2/6/2015 12:59:42 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman Final OK
|
GCE15-00019
| GCE-Permanent Service | 2/6/2015 | 2/6/2015 | 2/6/2015 12:09:38 PM | P | PASS |
|
|
Bill ###-#### or ###-#### PS, OH, N< Ok
|
ELE15-00316
| Electrical Rough-In | 2/6/2015 | 2/6/2015 | 2/6/2015 11:26:49 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman check for multi wire handle tie at final, RI ok to cover
|
ELE12-00762
| ELE-Aging Inspection | 2/6/2015 | 2/6/2015 | 2/6/2015 10:51:58 AM | | DONE |
|
|
|
ELE12-00762
| Final | 2/6/2015 | 2/6/2015 | 2/6/2015 10:51:49 AM | P | PASS |
|
|
Work completed on second permit. See ele12-00779
|
ELE14-03266
| Electrical Rough-In | 2/5/2015 | 2/6/2015 | 2/6/2015 10:21:24 AM | A | PASS |
|
|
soffit inspection Phone #: ###-#### Inspection requested via web by Chris Chesnut soffits ok to cover
|
ELE15-00320
| Conference | 2/5/2015 | 2/6/2015 | 2/6/2015 9:57:11 AM | A | DONE |
|
|
Calvin will be there. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan discussion of knob and tube, open splices, hidden junctions, previous repairs, and past permitting on the job.
|
ELE12-00804
| ELE-Aging Inspection | 2/6/2015 | 2/6/2015 | 2/6/2015 9:40:18 AM | | DONE |
|
|
Posted site, 2-6-15 9:40 am
|
ELE15-00313
| Temporary Service | 2/5/2015 | 2/6/2015 | 2/6/2015 9:27:34 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn TS, UG, N, OK
|
ELE15-00314
| Temporary Service | 2/5/2015 | 2/6/2015 | 2/6/2015 9:25:23 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn TS, UG, N, oK
|
ELE15-00316
| Electrical Rough-In | 2/5/2015 | 2/6/2015 | 2/6/2015 9:16:11 AM | A | FAIL |
|
|
New kitchen wiring Phone #: ###-#### Inspection requested via web by Emmet Bushman called contractor 300.13 (B) Device Removal. In multiwire branch circuits, the continuity of a grounded conductor shall not depend on device connections such as lampholders, receptacles, and so forth, where the removal of such devices would interrupt the continuity 300.4 1 nm through bored holes shall have protection where edge of hole is less than 1 1/4 inch from edge of framing member 300.4 2 where cable is run through notches in wood, it shall be protected by steel plate 210.4 B multi wire branch circuits shall have means to disconnect all ungrounded conductors simultaneously
|
ELE15-00315
| Final | 2/5/2015 | 2/6/2015 | 2/6/2015 8:45:21 AM | A | PASS |
|
|
###-#### please call karen 30 minutes in advance for access Phone #: ###-#### Inspection requested via web by danny perrin Final OK
|
ELE15-00315
| Permanent Service | 2/6/2015 | 2/6/2015 | 2/6/2015 8:44:37 AM | P | PASS |
|
|
###-#### please call karen 30 minutes in advance for access Phone #: ###-#### Inspection requested via web by danny perrine PS, UG, RC, OK
|
ELE12-02468
| ELE-Aging Inspection | 2/6/2015 | 2/6/2015 | 2/6/2015 6:09:16 AM | | DONE |
|
|
Talked to electrical contractor, project is back under construction and should be finishing soon
|
ELE15-00160
| Permanent Service | 2/5/2015 | 2/6/2015 | 2/5/2015 3:05:11 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov PS, UG, N, ok
|