Inspections for the day of: Friday, February 6, 2015.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00531 INSP-Sprinkler Rough-in2/5/20152/6/20152/6/2015 3:44:06 PMAPART
Rough-in inspection completed for living units only at tower 2 podium level. Install incomplete at the common area room 241. Also okayed prior C/N items at the 3rd and 4th floors tower 2. Note: * Damaged main and branchlines due to overheating by proximity to temporary jobsite heating appliances on the 2nd thru 5th floor corridors tower one to be replaced as discussed.*
FIR15-00026 INSP-Final Inspection2/5/20152/6/20152/6/2015 3:34:03 PMAPART
Overhead fire sprinkler modifications approved for cover at the grid ceilings.
FIR14-00919 INSP-Final Inspection2/5/20152/6/20152/6/2015 3:30:42 PMAPART
Overhead rough-in inspection passed. Need to provide matched response heads as noted.
FIR14-00304 INSP-Conference2/5/20152/6/20152/6/2015 11:57:34 AMADONE
Regarding sprinkler coverage at the corridor north side of annex one.