ELE20-00422
| Electrical Rough-In | 2/6/2020 | 2/6/2020 | 2/6/2020 1:56:37 PM | P | PASS |
|
|
Front walls Phone #: ###-#### Inspection requested via web by Dave Brueggemann Front walls rough in ok cover
|
ELE20-00436
| Temporary Service | 2/5/2020 | 2/6/2020 | 2/6/2020 11:14:49 AM | A | PASS |
|
|
200 amp temp service. Dan Cox Phone #: ###-#### Inspection requested via web by Dan Cox t/s u/g n ok
|
ELE19-03967
| Electrical Rough-In | 2/5/2020 | 2/6/2020 | 2/6/2020 10:52:13 AM | A | PASS |
|
|
Wall cover. Von is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Unable to confirm #10 minimum bond to panel board required by 517.14. Asked wireman and he stated provisions have been provided to install it. X-ray room walls rough in ok cover
|
ELE19-01592
| Final | 2/5/2020 | 2/6/2020 | 2/6/2020 10:21:04 AM | A | FAIL |
|
|
garage code is 9239 Phone #: ###-#### Inspection requested via web by Kevin Heideman 210.71- Each mandoor with grade level access shall have an exterior luminaire installed. Master bed mandoor open box at time of inspection. 300.15- All cables shall terminate in a box. 10-2 garage wall left of furnace just pushed back in wall.
|
ELE19-02693
| Final | 2/5/2020 | 2/6/2020 | 2/6/2020 8:55:48 AM | A | PASS |
|
|
Garage code 7927 Phone #: ###-#### Inspection requested via web by Dean Gernaat Final ok
|