Inspections for the day of: Thursday, February 6, 2020.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00422 Electrical Rough-In2/6/20202/6/20202/6/2020 1:56:37 PMPPASS
Front walls Phone #: ###-#### Inspection requested via web by Dave Brueggemann
Front walls rough in ok cover
ELE20-00436 Temporary Service2/5/20202/6/20202/6/2020 11:14:49 AMAPASS
200 amp temp service. Dan Cox Phone #: ###-#### Inspection requested via web by Dan Cox t/s u/g n ok
ELE19-03967 Electrical Rough-In2/5/20202/6/20202/6/2020 10:52:13 AMAPASS
Wall cover. Von is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Unable to confirm #10 minimum bond to panel board required by 517.14. Asked wireman and he stated provisions have been provided to install it. X-ray room walls rough in ok cover
ELE19-01592 Final2/5/20202/6/20202/6/2020 10:21:04 AMAFAIL
garage code is 9239 Phone #: ###-#### Inspection requested via web by Kevin Heideman 210.71- Each mandoor with grade level access shall have an exterior luminaire installed. Master bed mandoor open box at time of inspection.
300.15- All cables shall terminate in a box. 10-2 garage wall left of furnace just pushed back in wall.
ELE19-02693 Final2/5/20202/6/20202/6/2020 8:55:48 AMAPASS
Garage code 7927 Phone #: ###-#### Inspection requested via web by Dean Gernaat Final ok