FIR20-00069
| INSP-Final Inspection | 2/5/2020 | 2/6/2020 | 2/6/2020 2:06:01 PM | A | FAIL |
|
|
Permit failed based on noted deficiencies: induct smoke detector descriptors need to be corrected in Bld 1 and 2; Blding 2 office duct detector discriptor identified device as being in building 4; contractor to check all induct smoke detectors descriptors in B 1 and 2 for accuarcy before next inspection; B2 4th floor riser room inaccessible due to malfunctioning lock on door; B1 basement riser room device descriptors to identify location of devices in basement; B4 basement pull station descriptor identifies device being on 1st floor; B3 notification appliances on 1st floor near main lobby not in synch.
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Froese
|
FIR19-00230
| INSP-Final Inspection | 2/5/2020 | 2/6/2020 | 2/6/2020 2:04:56 PM | A | FAIL |
|
|
Permit failed based on noted deficiencies: induct smoke detector descriptors not correct (2nd fl ); basement riser room devices descriptors need to identify devices as being in the basement riser room. Contractor to coordinate with monitoring company to ensure accuracy of descriptors before next inspection. 2088990672 >> Inspection requested via mobile web by Josiah Froese
|
BLD06-02322
| FIRE-Final Inspection | 2/5/2020 | 2/6/2020 | | A | |
|
|
lee Phone #: ###-####
|