ELE01-02029
| Final | 2/6/2002 | 2/7/2002 | 2/7/2002 12:00:00 AM | A | FAIL |
|
|
###-#### outlets loose needs approved fixture MB closet 2/7/2002 12:03:32 PM
|
ELE02-00294
| Electrical Rough-In | 2/6/2002 | 2/7/2002 | 2/7/2002 12:00:00 AM | A | PASS |
|
|
###-#### r/i ok cover for electrode ok 2/7/2002 10:58:00 AM
|
ELE02-00328
| Final | 2/6/2002 | 2/7/2002 | 2/7/2002 12:00:00 AM | A | FAIL |
|
|
###-#### BRIAN cor. and $42.00 fee due posted called 250.53(g) grd rod driven at less than 45 degrees 110.3(b) needs square D breakers 358.10 emt not approved in dirt without protection, 200.6 shall not not I D 6 or smaller neutral 2/7/2002 11:33:06 AM
|
ELE01-03861
| Final | 2/7/2002 | 2/7/2002 | 2/7/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 02/07/2002 at 06:45:51. Contact: ###-####. ok final had no access early AM gates locked 2/7/2002 2:09:54 PM
|
ELE02-00323
| Temporary Service | 2/7/2002 | 2/7/2002 | 2/7/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 02/07/2002 at 08:53:04. Contact: ###-####. t/s u/g new ok 2/7/2002 3:10:25 PM
|
ELE02-00322
| Temporary Service | 2/7/2002 | 2/7/2002 | 2/7/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 02/07/2002 at 08:54:09. Contact: ###-####. t/s u/g new ok 2/7/2002 3:14:58 PM
|
ELE02-00230
| Temporary Service | 2/7/2002 | 2/7/2002 | 2/7/2002 12:00:00 AM | P | PASS |
|
|
###-#### RICK t/s u/g new ok 2/7/2002 3:41:14 PM
|