Inspections for the day of: Friday, February 7, 2003.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02728 Final2/5/20032/7/20032/7/2003 12:00:00 AMAFAIL
call first ###-#### or ###-#### shop, hobby area needs gfci all recepts,install 220 volt recept, and room a/c shall meet NEC 440.65 2/7/2003 8:26:47 AM
ELE03-00330 Temporary Service2/6/20032/7/20032/7/2003 12:00:00 AMAFAIL
###-#### could not locate called left message 2/7/2003 10:02:09 AM
ELE03-00292 Electrical Rough-In2/6/20032/7/20032/7/2003 12:00:00 AMAFAIL
ufer grnd; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung cor. posted called 250.52(A)(3) shall encase all 20 ft of conductor not 15 ft of it 2/7/2003 9:30:48 AM
ELE03-00291 Temporary Service2/6/20032/7/20032/7/2003 12:00:00 AMACANC
t/p for "b"--lloyd ###-#### needs a permit for each t/p , this permit # already used for other t/s 2/7/2003 10:27:07 AM
ELE03-00298 Electrical Rough-In2/6/20032/7/20032/7/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/6/2003 at 3:08:56 PM. Contact: ###-####. 300.4 11/4 for MC 2/7/2003 8:50:38 AM
ELE03-00226 Electrical Rough-In2/7/20032/7/20032/7/2003 12:00:00 AMPFAIL
under.grnd; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung cor. posted needs 18 inches as 300.5 tables states for depth called 2/7/2003 1:56:38 PM
ELE03-00340 Permanent Service2/7/20032/7/20032/7/2003 12:00:00 AMPPASS
###-#### p/s o/h rec. ok 2/7/2003 12:13:15 PM
ELE02-01458 Electrical Rough-In2/7/20032/7/20032/7/2003 12:00:00 AMPPART
###-#### ceiling ok 2/7/2003 1:21:14 PM
ELE03-00267 Electrical Rough-In2/7/20032/7/20032/7/2003 12:00:00 AMPPART
TRENCH; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung u/g ok 2/7/2003 3:28:24 PM
ELE03-00298 Electrical Rough-In2/7/20032/7/20032/7/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 2/7/2003 at 9:03:43 AM. Contact: ###-####. ceiling ok 2/7/2003 12:36:36 PM
ELE01-03617 Electrical Rough-In2/7/20032/7/20032/7/2003 12:00:00 AMPPART
area B east, and 2nd floor rotunda area ceilings and soffits 2/7/2003 2:54:24 PM