Inspections for the day of: Monday, February 7, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00639 FIR-Aging Inspection2/7/20052/7/20052/7/2005 12:00:00 AM NR
wip 2/7/2005 4:29:42 PM
FIR04-00655 INSP-Final Inspection2/4/20052/7/20052/7/2005 12:00:00 AMAFAIL
Provide verification duct smoke detectors are not required. Provide high/low pressure switch monitoring. Test waterflow. Provide map at facp. Not receiving phone line 2 trouble or the battery troubles. Provide signage for the riser door. Provide nfpa 72 forms 2/7/2005 11:37:06 AM
FIR05-00047 INSP-Sprinkler Rough-in2/4/20052/7/20052/7/2005 12:00:00 AMAPART
karrie; Phone #: ###-#### Sprinklers under the stairs are ok to cover but will require submittal to show additional work. No more covers to be given unless the work is shown. 2/7/2005 10:04:38 AM
FIR04-00810 INSP-Final Inspection2/4/20052/7/20052/7/2005 12:00:00 AMAFAIL
Could not give final due to ceiling tile not being installed. Sprinkler piping is ok to cover. 2/7/2005 8:31:01 AM
BLD04-02592 FIRE-Alarm Testing2/4/20052/7/20052/7/2005 12:00:00 AMAPASS
Fire life safety finaled 2/7/2005 11:57:52 AM
BLD04-02836 FIRE-Final Inspection2/4/20052/7/20052/7/2005 12:00:00 AMAPASS
Fire life safety finaled 2/7/2005 10:37:31 AM
FIR04-00754 INSP-Alarm Testing2/7/20052/7/20052/7/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/7/2005 at 6:16:19 AM. Contact: ###-####.
FIR03-00440 INSP-Final Inspection2/7/20052/7/20052/7/2005 12:00:00 AMAPASS
Electrical outlets relocated from under hood. Permit finaled
BLD04-00888 FIRE-Final Inspection2/7/20052/7/20052/7/2005 12:00:00 AMPPASS
fire alarm and fire life safety finaled
BLD03-02084 FIRE-Conference2/7/20052/7/20052/7/2005 12:00:00 AMPDONE
A stop work order has been issued and posted at the project for any fire alarm installation work after 2/7/05 at Mary's direction. Stop work order given to the superintendant at job site.
FIR04-00608 INSP-Final Inspection2/4/20052/7/20052/7/2005 12:00:00 AMPFAIL
Provide test papers and repair the inconsistant flow alarm for the DBSI riser. 2/7/2005 4:28:12 PM
BLD04-01734 FIRE-Final Inspection2/7/20052/7/20052/7/2005 12:00:00 AMPPASS
fire life safety finaled 2/7/2005 1:15:05 PM
BLD04-00838 FIRE-Final Inspection2/7/20052/7/20052/7/2005 12:00:00 AMPPASS
Fire life safety finaled 2/7/2005 1:50:52 PM
BLD04-02782 FIRE-Final Inspection2/7/20052/7/20052/7/2005 12:00:00 AMPFAIL
Address on suite does not match permit. Submit change of address. Provide fire alarm permit for the two new duct smoke detectors that need tied into the fire alarm system. 2/7/2005 4:26:56 PM