FIR04-00639
| FIR-Aging Inspection | 2/7/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | | NR |
|
|
wip 2/7/2005 4:29:42 PM
|
FIR04-00655
| INSP-Final Inspection | 2/4/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | A | FAIL |
|
|
Provide verification duct smoke detectors are not required. Provide high/low pressure switch monitoring. Test waterflow. Provide map at facp. Not receiving phone line 2 trouble or the battery troubles. Provide signage for the riser door. Provide nfpa 72 forms 2/7/2005 11:37:06 AM
|
FIR05-00047
| INSP-Sprinkler Rough-in | 2/4/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | A | PART |
|
|
karrie; Phone #: ###-#### Sprinklers under the stairs are ok to cover but will require submittal to show additional work. No more covers to be given unless the work is shown. 2/7/2005 10:04:38 AM
|
FIR04-00810
| INSP-Final Inspection | 2/4/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | A | FAIL |
|
|
Could not give final due to ceiling tile not being installed. Sprinkler piping is ok to cover. 2/7/2005 8:31:01 AM
|
BLD04-02592
| FIRE-Alarm Testing | 2/4/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 2/7/2005 11:57:52 AM
|
BLD04-02836
| FIRE-Final Inspection | 2/4/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 2/7/2005 10:37:31 AM
|
FIR04-00754
| INSP-Alarm Testing | 2/7/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/7/2005 at 6:16:19 AM. Contact: ###-####.
|
FIR03-00440
| INSP-Final Inspection | 2/7/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | A | PASS |
|
|
Electrical outlets relocated from under hood. Permit finaled
|
BLD04-00888
| FIRE-Final Inspection | 2/7/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | P | PASS |
|
|
fire alarm and fire life safety finaled
|
BLD03-02084
| FIRE-Conference | 2/7/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | P | DONE |
|
|
A stop work order has been issued and posted at the project for any fire alarm installation work after 2/7/05 at Mary's direction. Stop work order given to the superintendant at job site.
|
FIR04-00608
| INSP-Final Inspection | 2/4/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | P | FAIL |
|
|
Provide test papers and repair the inconsistant flow alarm for the DBSI riser. 2/7/2005 4:28:12 PM
|
BLD04-01734
| FIRE-Final Inspection | 2/7/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 2/7/2005 1:15:05 PM
|
BLD04-00838
| FIRE-Final Inspection | 2/7/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety finaled 2/7/2005 1:50:52 PM
|
BLD04-02782
| FIRE-Final Inspection | 2/7/2005 | 2/7/2005 | 2/7/2005 12:00:00 AM | P | FAIL |
|
|
Address on suite does not match permit. Submit change of address. Provide fire alarm permit for the two new duct smoke detectors that need tied into the fire alarm system. 2/7/2005 4:26:56 PM
|