Inspections for the day of: Tuesday, February 7, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00199 Final2/7/20062/7/20062/7/2006 4:22:18 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: joe wheeler cor. called 410.14(B) shall provide access to box behind fixture bathrm
ELE06-00422 Electrical Rough-In2/6/20062/7/20062/7/2006 4:04:03 PMPCANC
any questions please call Matt Beglan; Phone #: ###-#### Internet Inspection Request from: Jeff Radford called I rescheduled inspection for 02-08-06 AM at the request of contractor because his electrician quits work at 3:30 Pm and he wanted to be at job site when I do inspection
ELE05-03215 Permanent Service2/7/20062/7/20062/7/2006 3:28:45 PMPPASS
Rick; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong p/s u/g new ok
ELE05-04285 Electrical Rough-In2/6/20062/7/20062/7/2006 2:57:08 PMPPASS
Scheduled by a contractor via Hello! on 2/6/2006 at 3:36:35 PM. Contact: ###-####. ceilings ok
ELE05-03999 Final2/7/20062/7/20062/7/2006 1:51:05 PMPPASS
perm occupancy ok question on xray listing verified no card at site
ELE05-03582 Final2/7/20062/7/20062/7/2006 1:36:26 PMPFAIL
Brandon; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
cor. called 210.11(C)(3) pantry outlet shall not be on bath circuit, no power to recept below window in kit (counter) secure outside cover so they don't fall off when testing recept
ELE06-00395 Permanent Service2/7/20062/7/20062/7/2006 12:16:42 PMPPASS
chad; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s only p/s o/h rec. ok
ELE06-00423 Electrical Rough-In2/6/20062/7/20062/7/2006 10:49:24 AMAFAIL
###-#### - brandon cor. called 300.4 nail plates & 11/4" inside and outside edges of studs, 314.20 outside box shall be flush with siding, 314.17 needs conn for romex at bell box, still needs u/g inspection
ELE06-00199 Electrical Rough-In2/6/20062/7/20062/7/2006 10:12:52 AMAPASS
ceiling inspection; Phone #: ###-#### Internet Inspection Request from: joe wheeler ok
ELE06-00421 Final2/6/20062/7/20062/7/2006 9:53:12 AMAFAIL
please do a final inspection.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH needs clearence over roof 2" mast, bring grounding up to code and clearence for panel note no violations to be retained called cor. posted
ELE05-03127 Electrical Rough-In2/6/20062/7/20062/7/2006 9:14:40 AMAPASS
John; Phone #: ###-#### Internet Inspection Request from: Elizabeth
basement and kit ok
ELE06-00165 Electrical Rough-In2/6/20062/7/20062/7/2006 8:39:43 AMAPART
Scheduled by a contractor via Hello! on 2/6/2006 at 3:49:56 PM. Contact: ###-####. phone , power u/g in building slab
ELE05-04417 ELE-Aging Inspection2/7/20062/7/20062/7/2006 8:16:51 AM PART
wsuc
ELE06-00395 Electrical Rough-In2/7/20062/7/20062/7/2006 12:00:00 AMPPART
chad; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s ok still needs to address sub panel , feeds to range and dryer
ELE05-03127 Rough-In Permanent Service2/6/20062/7/20062/6/2006 4:23:02 PMACANC
John; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong Inspection cancelled from web by: Elizabeth Esong