ELE06-02976
| ELE-Request for Extension | 2/5/2007 | 2/6/2006 | | A | |
|
|
pls extend
|
ELE05-01575
| ELE-Aging Inspection | 2/7/2006 | 2/7/2006 | 2/8/2006 4:09:08 PM | | DONE |
|
|
see final
|
ELE05-01344
| ELE-Aging Inspection | 2/7/2006 | 2/7/2006 | 2/7/2006 4:19:23 PM | | DONE |
|
|
see final
|
ELE05-03599
| Final | 2/7/2006 | 2/7/2006 | 2/7/2006 4:18:56 PM | P | FAIL |
|
|
Dan -- call 1st before insp for key access; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr,left corr notice,210.52(H) hallway over 10' shall have receptacle, 406.5 recpt faceplate shall seat against mounting surface(library), 404.4 switch shall not be installed in tub area,440.6(A) min breaker size for a/c shall be 45A, 430.107 pump motor disconnect shall be readily accessible,680.73 electrical equipment for tub shall be accessible without damaging building, 408.4 circuit directory shall be complete and specific for each circuit (identify 2 small appliance branch circuits in kitchen)
|
ELE05-01344
| Final | 2/7/2006 | 2/7/2006 | 2/7/2006 3:07:38 PM | P | PASS |
|
|
Internet Inspection Request from: Jeff Radford called contr, left survey, 400.8(1) cord shall not be used as a substitute for fixed wiring (water heater)
|
ELE05-01492
| ELE-Aging Inspection | 2/7/2006 | 2/7/2006 | 2/7/2006 3:02:56 PM | | DONE |
|
|
see final
|
ELE05-03278
| Final | 2/7/2006 | 2/7/2006 | 2/7/2006 2:43:10 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr, bldr, left corr notice, 110.26(A)(1) depth of working space shall be 3' in front of panel. no cards available for occupancy.
|
ELE06-00430
| Electrical Rough-In | 2/7/2006 | 2/7/2006 | 2/7/2006 2:12:31 PM | P | PASS |
|
|
work being done in WIC area at Central District Health Department, please contact Bill, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters walls only ok to cover
|
ELE06-00414
| Temporary Service | 2/7/2006 | 2/7/2006 | 2/7/2006 12:56:02 PM | P | PASS |
|
|
Verna; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong t/s u/g n ok
|
ELE06-00426
| Permanent Service | 2/6/2006 | 2/7/2006 | 2/7/2006 10:34:38 AM | A | CANC |
|
|
###-#### - mike see final
|
ELE06-00397
| Final | 2/3/2006 | 2/7/2006 | 2/7/2006 10:10:32 AM | A | PASS |
|
|
call allison for access ###-####; Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final
|
ELE06-00353
| Permanent Service | 2/6/2006 | 2/7/2006 | 2/7/2006 10:07:30 AM | A | FAIL |
|
|
Service Inspection Please call Steve Ruter ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson called contr, left corr notice, 250.142(B) gnded circuit conductor shall not be used for grounding non-current carrying metal parts of equip,314.28(A)(2) angle pulls shall not be less than 6 times the size of the largest raceway plus the sum of the diameters of all other raceways in the same row on the same side of the box, 517.13(A) patient care areas shall be provided with a ground path for fault current in a cable that qualifies as an equipment grounding return path per 250.118. Took green sticker down.
|
ELE06-00314
| Electrical Rough-In | 2/6/2006 | 2/7/2006 | 2/7/2006 9:22:31 AM | A | PASS |
|
|
conduit cover inspection, please contact Matt, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters u/g for parking lot lights ok to cover
|
ELE05-04507
| Final | 2/6/2006 | 2/7/2006 | 2/7/2006 8:35:54 AM | A | CANC |
|
|
kevin ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see ri
|
ELE05-03278
| Final | 2/7/2006 | 2/7/2006 | 2/7/2006 8:13:10 AM | A | NR |
|
|
Spoke to Bob Reichart last Thursday concerning lights on Niblett side of building. Factory miship on the lighting and they will use floor lighting until lights can be reshipped.; Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr about permit, water heater, and panel space. told to recall for final
|
ELE05-04507
| Electrical Rough-In | 2/7/2006 | 2/7/2006 | 2/7/2006 12:00:00 AM | A | PASS |
|
|
kevin ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, met with excavator, ok to cover parking lot lights u/g only
|
ELE06-00426
| Final | 2/7/2006 | 2/7/2006 | 2/7/2006 12:00:00 AM | A | PASS |
|
|
###-#### - mike p/s u/g reconnect ok
|
ELE05-01492
| Final | 2/7/2006 | 2/7/2006 | 2/7/2006 12:00:00 AM | P | PASS |
|
|
ok to final
|
ELE06-00314
| Electrical Rough-In | 2/6/2006 | 2/7/2006 | 2/6/2006 4:13:45 PM | P | CANC |
|
|
conduit cover isnspection, please contact Matt, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters Inspection cancelled from web by: Wendy Waters
|