Inspections for the day of: Tuesday, February 7, 2006.
Number of inspections: 19
Percentage of inspections complete: 95 %
Percentage of inspections not complete: 5 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02976 ELE-Request for Extension2/5/20072/6/2006 A 
pls extend
ELE05-01575 ELE-Aging Inspection2/7/20062/7/20062/8/2006 4:09:08 PM DONE
see final
ELE05-01344 ELE-Aging Inspection2/7/20062/7/20062/7/2006 4:19:23 PM DONE
see final
ELE05-03599 Final2/7/20062/7/20062/7/2006 4:18:56 PMPFAIL
Dan -- call 1st before insp for key access; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr,left corr notice,210.52(H) hallway over 10' shall have receptacle, 406.5 recpt faceplate shall seat against mounting surface(library), 404.4 switch shall not be installed in tub area,440.6(A) min breaker size for a/c shall be 45A, 430.107 pump motor disconnect shall be readily accessible,680.73 electrical equipment for tub shall be accessible without damaging building, 408.4 circuit directory shall be complete and specific for each circuit (identify 2 small appliance branch circuits in kitchen)
ELE05-01344 Final2/7/20062/7/20062/7/2006 3:07:38 PMPPASS
Internet Inspection Request from: Jeff Radford called contr, left survey, 400.8(1) cord shall not be used as a substitute for fixed wiring (water heater)
ELE05-01492 ELE-Aging Inspection2/7/20062/7/20062/7/2006 3:02:56 PM DONE
see final
ELE05-03278 Final2/7/20062/7/20062/7/2006 2:43:10 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr, bldr, left corr notice, 110.26(A)(1) depth of working space shall be 3' in front of panel. no cards available for occupancy.
ELE06-00430 Electrical Rough-In2/7/20062/7/20062/7/2006 2:12:31 PMPPASS
work being done in WIC area at Central District Health Department, please contact Bill, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters walls only ok to cover
ELE06-00414 Temporary Service2/7/20062/7/20062/7/2006 12:56:02 PMPPASS
Verna; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong t/s u/g n ok
ELE06-00426 Permanent Service2/6/20062/7/20062/7/2006 10:34:38 AMACANC
###-#### - mike see final
ELE06-00397 Final2/3/20062/7/20062/7/2006 10:10:32 AMAPASS
call allison for access ###-####; Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final
ELE06-00353 Permanent Service2/6/20062/7/20062/7/2006 10:07:30 AMAFAIL
Service Inspection Please call Steve Ruter ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson called contr, left corr notice, 250.142(B) gnded circuit conductor shall not be used for grounding non-current carrying metal parts of equip,314.28(A)(2) angle pulls shall not be less than 6 times the size of the largest raceway plus the sum of the diameters of all other raceways in the same row on the same side of the box, 517.13(A) patient care areas shall be provided with a ground path for fault current in a cable that qualifies as an equipment grounding return path per 250.118. Took green sticker down.
ELE06-00314 Electrical Rough-In2/6/20062/7/20062/7/2006 9:22:31 AMAPASS
conduit cover inspection, please contact Matt, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters u/g for parking lot lights ok to cover
ELE05-04507 Final2/6/20062/7/20062/7/2006 8:35:54 AMACANC
kevin ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see ri
ELE05-03278 Final2/7/20062/7/20062/7/2006 8:13:10 AMANR
Spoke to Bob Reichart last Thursday concerning lights on Niblett side of building. Factory miship on the lighting and they will use floor lighting until lights can be reshipped.; Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr about permit, water heater, and panel space. told to recall for final
ELE05-04507 Electrical Rough-In2/7/20062/7/20062/7/2006 12:00:00 AMAPASS
kevin ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, met with excavator, ok to cover parking lot lights u/g only
ELE06-00426 Final2/7/20062/7/20062/7/2006 12:00:00 AMAPASS
###-#### - mike p/s u/g reconnect ok
ELE05-01492 Final2/7/20062/7/20062/7/2006 12:00:00 AMPPASS
ok to final
ELE06-00314 Electrical Rough-In2/6/20062/7/20062/6/2006 4:13:45 PMPCANC
conduit cover isnspection, please contact Matt, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters Inspection cancelled from web by: Wendy Waters