FIR07-00046
| INSP-Final Inspection | 2/6/2007 | 2/7/2007 | 2/8/2007 9:40:55 AM | P | CANC |
|
|
Per todd the canopies had to be reordered.
|
FIR06-00651
| INSP-Alarm Testing | 2/6/2007 | 2/7/2007 | 2/8/2007 9:17:51 AM | P | FAIL |
|
|
See Mike Timmermans entry from 2/7/2006
|
FIR07-00066
| INSP-Final Inspection | 2/5/2007 | 2/7/2007 | 2/8/2007 9:16:31 AM | A | PASS |
|
|
Hood suppression system operated correctly
|
FIR06-01010
| INSP-Sprinkler Rough-in | 2/6/2007 | 2/7/2007 | 2/8/2007 7:43:31 AM | P | PASS |
|
|
Underground piping is ok for cover
|
FIR05-00479
| INSP-Final Inspection | 2/6/2007 | 2/7/2007 | 2/7/2007 3:51:09 PM | A | PASS |
|
|
Permit finaled. Inspection was performed by Brian Johnson
|
FIR06-00949
| INSP-Final Inspection | 2/6/2007 | 2/7/2007 | 2/7/2007 3:27:11 PM | P | PASS |
|
|
Permit finaled
|
FIR06-00222
| INSP-Final Inspection | 2/6/2007 | 2/7/2007 | 2/7/2007 3:26:02 PM | P | FAIL |
|
|
Need to have the pendant within 12" of the riser and the piping under the floor is still not insulated.
|
FIR05-00574
| INSP-Final Inspection | 2/7/2007 | 2/7/2007 | 2/7/2007 3:22:10 PM | P | CANC |
|
|
I could not make it there when Lori the state elevator inspector was to be there. Per Matt it will be rescheduled for next week
|
FIR06-00974
| INSP-Final Inspection | 2/7/2007 | 2/7/2007 | 2/7/2007 1:06:58 PM | P | PASS |
|
|
Permit finaled
|
FIR06-00910
| INSP-Final Inspection | 2/7/2007 | 2/7/2007 | 2/7/2007 1:06:21 PM | P | PASS |
|
|
Permit finaled
|
BLD06-02349
| FIRE-Final Inspection | 2/6/2007 | 2/7/2007 | 2/7/2007 1:05:35 PM | A | FAIL |
|
|
The fire permit for the hood supression system needs finaling and all exit signs/emergency lights need to be installed/tested per the city approved plans.
|
FIR06-00944
| INSP-Final Inspection | 2/5/2007 | 2/7/2007 | 2/7/2007 11:07:08 AM | A | CANC |
|
|
To be rescheduled per george for tomorrow morining at 8:00
|
FIR07-00004
| INSP-Final Inspection | 2/6/2007 | 2/7/2007 | 2/7/2007 10:47:22 AM | A | FAIL |
|
|
Ceiling tile is not installed and the approved plans are still not on site.
|
FIR06-00942
| INSP-Final Inspection | 2/5/2007 | 2/7/2007 | 2/7/2007 10:41:10 AM | A | PASS |
|
|
permit finaled
|
FIR07-00012
| INSP-Final Inspection | 2/6/2007 | 2/7/2007 | 2/7/2007 9:26:09 AM | A | FAIL |
|
|
Tested the interconnection of the NAC and the facp which passed. Found that the duct smoke detectors did not shut down the hvac units. They will need to be corrected and notification tested and cd verified.
|
FIR06-00970
| INSP-Final Inspection | 2/6/2007 | 2/7/2007 | 2/7/2007 9:24:20 AM | A | PASS |
|
|
permit finaled
|