FIR07-00468
| INSP-Alarm Testing | 2/7/2008 | 2/7/2008 | 2/7/2008 4:51:17 PM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 2/7/2008 at 6:58:30 AM.
|
BLD06-03523
| FIRE-Final Inspection | 2/6/2008 | 2/7/2008 | 2/7/2008 4:51:03 PM | A | CANC |
|
|
justin Phone #: ###-####
|
FIR06-00986
| INSP-Final Inspection | 2/6/2008 | 2/7/2008 | 2/7/2008 4:49:05 PM | P | FAIL |
|
|
Missing several items for final at the riser similar to the adjacent building #2. Not ready for final due to missing and defficient items.
|
FIR06-00985
| INSP-Final Inspection | 2/6/2008 | 2/7/2008 | 2/7/2008 4:46:30 PM | P | FAIL |
|
|
Provide clearance at the riser/floor slab, missing sprinkler coverage at the riser, missing "911" sign at the bell, provide signage at the floor control valves indicating what system is served, missing orfice at the inspectors test, not all items for final reviewed at this time due to number of defficiencies found.
|
FIR07-00083
| INSP-Final Inspection | 2/6/2008 | 2/7/2008 | 2/7/2008 4:42:57 PM | P | PASS |
|
|
Fire alarm permit work passed inspection, minor field mods are acceptable, signage at the FACP room door to be provided and verified at life safety final, building addressing corrected while on site per account information, permit finaled.
|
FIR07-00049
| INSP-Final Inspection | 2/6/2008 | 2/7/2008 | 2/7/2008 4:40:04 PM | P | PASS |
|
|
Fire alarm testing completed satisfactory, need to provide signage at the door to the FACP room, building addressing per the account corrected while on site.
|
FIR07-00662
| INSP-Alarm Testing | 2/6/2008 | 2/7/2008 | 2/7/2008 3:37:57 PM | A | PASS |
|
|
Completed balance of fire alarm testing including initiation devices on the 3rd and 4th floors, dampers at all floors-(non-functional dampers at the west end floors 1-4 repaired while on site), elevator recall, EOL voltage, closure at one door repaired while on site, signals and account checked, and reinspected noted defficiencies from the previous day for compliance. Need to provide building map at the panel including all initiation devices and their locations per review notes and as discussed, fire alarm permit work approved for final.
|
BLD06-01671
| FIRE-Final Inspection | 2/7/2008 | 2/7/2008 | 2/7/2008 11:39:40 AM | P | PASS |
|
|
Fire life safety finaled.
|
BLD06-01671
| BLD-Aging Inspection | 2/6/2008 | 2/7/2008 | 2/7/2008 11:38:27 AM | A | PASS |
|
|
Project is okay for final per project activities and previous inspection completed 4/19/07.
|
BLD07-02967
| FIRE-Final Inspection | 2/6/2008 | 2/7/2008 | 2/7/2008 11:12:10 AM | A | PASS |
|
|
Remainder of the scope of work passed fire life safety inspection.
|
FIR08-00042
| INSP-Final Inspection | 2/5/2008 | 2/7/2008 | 2/7/2008 11:11:17 AM | A | PASS |
|
|
Fire alarm modifications passed field testing, permit finaled.
|
FIR08-00046
| INSP-Final Inspection | 2/7/2008 | 2/7/2008 | 2/7/2008 12:00:00 AM | P | PASS |
|
|
Corrections made per last inspection. KR
|