Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-02358 BLD-Aging Inspection2/7/20082/7/20082/11/2008 2:39:16 PMANR
Inspection will be called in tomorrow.
BLD07-02296 BLD-Aging Inspection2/7/20082/7/20082/8/2008 1:23:25 PMPPASS
Life safety passed.
FIR07-00697 INSP-Sprinkler Rough-in2/6/20082/7/20082/7/2008 4:40:39 PMPCANC
Inspection canceled due to time constraints. (Micron plan review) Mike M. was notified of this midmorning.
FIR08-00009 INSP-Final Inspection2/6/20082/7/20082/7/2008 3:37:01 PMPPASS
permit finaled
BLD05-02608 BLD-Aging Inspection2/6/20082/7/20082/7/2008 3:35:59 PMAFAIL
All items except the exit sign/emergency light in the east corridor has been checked off. A re-inspection is set up for next wednesday.
BLD07-03072 FIRE-Final Inspection2/6/20082/7/20082/7/2008 12:49:02 PMPPASS
fire life safety passed.
FIR07-01013 INSP-Sprinkler Rough-in2/5/20082/7/20082/7/2008 12:48:25 PMAPART
The overbuilds need to be filled with insulation as per the approved drawings. A hanger/block assembly on the wet system needs replaced. Tenting needs repaired. The inspectors test for the dry system needs to be located at the end of the most remote branchline as stated in NFPA 13 8.16.4