Inspections for the day of: Monday, February 7, 2011.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02499 ELE-Aging Inspection2/7/20112/7/20112/8/2011 6:36:10 AM DONE
contractor to call when available
ELE10-02500 ELE-Aging Inspection2/7/20112/7/20112/8/2011 6:35:29 AM DONE
contractor to call when available
ELE10-02861 Final2/2/20112/7/20112/7/2011 3:30:19 PMPFAIL
Requesting Electrical Final on new office addition. Phone #: ###-#### >> Inspection requested via web by Tim Lawrence called, left correction notice, NEC 210.8(B)(5) shall provide gfci protection for receptacles within 6' of sink-15and 20A, BCC shall provide dual level switching per plans for office lighting, BCC panel schedule shall be correct per NEC 408.4
ELE11-00137 Final2/7/20112/7/20112/7/2011 3:03:29 PMPPASS
Pleae ask for Ron at the front desk. If any problems/corrections call Jeff Creek ###-####. Thanks. Phone #: ###-#### x0000 >> Inspection requested via web by Andrea Creek ok final, no card to sign
ELE10-02378 Permanent Service2/7/20112/7/20112/7/2011 2:05:30 PMPPASS
Need inspection of service upgrade. Phone #: ###-#### >> Inspection requested via web by Alan Lusk check ser connections, p/s u/g rec ok
ELE11-00242 Electrical Rough-In2/7/20112/7/20112/7/2011 1:20:30 PMPPASS
please give me half an hour notice to insure access thanks shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman ri ok
ELE10-02847 Final2/7/20112/7/20112/7/2011 12:39:31 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Zane Robertson ok final, signed card
ELE11-00110 Final2/4/20112/7/20112/7/2011 10:12:57 AMAPASS
Dave Phone #: ###-#### ok final
ELE11-00231 Final2/7/20112/7/20112/7/2011 9:36:18 AMACANC
Final for temp power. Please call if there are any questions. Thanks. Eric Phone #: ###-#### >> Inspection requested via web by Eric Schroeder see t/s
ELE11-00231 Temporary Service2/7/20112/7/20112/7/2011 9:35:54 AMAPASS
Final for temp power. Please call if there are any questions. Thanks. Eric Phone #: ###-#### >> Inspection requested via web by Eric Schroeder t/s u/g n ok
ELE11-00111 Final2/4/20112/7/20112/7/2011 9:20:56 AMAPASS
Dave Phone #: ###-#### ok final
ELE10-02847 Final2/4/20112/7/20112/7/2011 8:51:37 AMAPART
Phone #: ###-#### >> Inspection requested via web by Zane Robertson ok cover ceiling, left correction notice, NEC 110.12(A) shall close unused openings, 210.8(B)(5) shall provide gfci protection for receptacles within 6' of sink, 362.30 shall strap ent within 3' of box
ELE10-02498 ELE-Aging Inspection2/7/20112/7/20112/7/2011 6:41:02 AM DONE
contractor will call for final when he is available
ELE10-02525 ELE-Aging Inspection2/7/20112/7/20112/7/2011 6:39:49 AM DONE
contractor will call for inspection when he is available
ELE10-01493 ELE-Aging Inspection2/7/20112/7/20112/7/2011 6:36:56 AM DONE
no activity, still under construction
ELE09-01934 ELE-Aging Inspection2/7/20112/7/20112/7/2011 6:35:36 AM DONE
no activity, still under construction
ELE09-01497 ELE-Aging Inspection2/7/20112/7/20112/7/2011 6:33:55 AM DONE
waiting for call to final