BLD10-02415
| FIRE-Conference | 2/7/2011 | 2/7/2011 | 2/7/2011 3:12:58 PM | P | DONE |
|
|
Discussion with contractor regarding fire extinguisher locations, project related trade permits, finish schedule, review notes, etc.
|
FIR10-00535
| FIR-Aging Inspection | 2/7/2011 | 2/7/2011 | 2/7/2011 3:10:37 PM | | DONE |
|
|
|
FIR10-00524
| FIR-Aging Inspection | 2/7/2011 | 2/7/2011 | 2/7/2011 3:09:14 PM | | DONE |
|
|
Site visit determined work is finished. Pending final inspection request per conversation with building rep.
|
FIR10-00632
| INSP-Final Inspection | 2/7/2011 | 2/7/2011 | 2/7/2011 3:01:36 PM | P | PASS |
|
|
Fire alarm permit okay for final.
|
FIR11-00001
| INSP-Final Inspection | 2/4/2011 | 2/7/2011 | 2/7/2011 2:58:45 PM | P | NR |
|
|
Hood suppression system test pending exhaust fan/ make-up air functions.
|
BLD10-02371
| FIRE-Final Inspection | 2/4/2011 | 2/7/2011 | 2/7/2011 2:55:43 PM | P | FAIL |
|
|
Final pending project related fire sprinkler permit work, modifications to the existing fire alarm panel appear to have been done without a permit ( AES radio subscriber unit added), missing stamped plan set and fire code review notes, scope of work appears to exceed project description, missing a fire extinguisher within travel distance req. for the new office area.
|
FIR11-00016
| INSP-Final Inspection | 2/4/2011 | 2/7/2011 | 2/7/2011 2:50:07 PM | A | FAIL |
|
|
Missing escutcheons at the new office areas, covered head at one closet, patio at the north side is still missing a sidewall head- provide coverage per plan or document with a plan modification including reason deleted.
|
BLD11-00204
| FIRE-Final Inspection | 2/4/2011 | 2/7/2011 | 2/7/2011 11:36:16 AM | A | PASS |
|
|
Fire life safety inspection completed satisfactory with the exception of missing signage at the main entry/exit and compliance with item #2 on correction notice dated 1/24/11 regarding signage at the game room door.
|