FIR10-00494 INSP-Final Inspection2/4/20112/7/20112/7/2011 3:07:03 PMPCANC
Permit is not ready for final. See "rough-in" inspection notes.
FIR10-00494 INSP-Sprinkler Rough-in/Hydro2/4/20112/7/20112/7/2011 3:02:04 PMPFAIL
See the city approved plans/notes for items marked. They include pump room ventilation, pump room emergency lighting, additional sprinkler coverage in the pump room and 12 missing ESFR heads near the pump room and a hydro test.
FIR10-00645 INSP-Final Inspection2/4/20112/7/20112/7/2011 2:59:45 PMPPASS
Permit finaled
FIR10-00655 INSP-Sprinkler Rough-in2/7/20112/7/20112/7/2011 2:58:06 PMPPASS
The tenting in the kitchen and entry areas appears adequate.
FIR09-00082 INSP-Final Inspection2/4/20112/7/20112/7/2011 1:24:23 PMAFAIL
Three tamper switches need to be adjusted. This includes two in the valve pit and one on the jockey pump.
FIR10-00593 INSP-Final Inspection2/3/20112/7/20112/7/2011 11:29:30 AMAFAIL
The latest plan modifications took out some of the scope of work. Plans will need to be resubmitted showing all of the fire alarm work or an additional permit will be required for this work. I went ahead and witnessed the functionality of the notification circuit. To final this permit plans will just need to match the work performed.