Inspections for the day of: Wednesday, February 7, 2018.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01032 Electrical Rough-In2/7/20182/7/20182/7/2018 3:05:32 PMPPASS
Inspection for cover:
Janitors Closets on floors 1-4, 4th floor corridor, Unit 402 east wall, Unit 320 soffits, 1st floor fire damper Phone #: ###-#### Inspection requested via web by Scott Wilson
Areas as noted on print ok to cover.
Talked about lockable disc for dampers in hallways as per 110.25
ELE18-00369 Electrical Rough-In2/6/20182/7/20182/7/2018 1:41:59 PMPFAIL
Added washer/dryer circuits @ 2 locations and additional 120v. 20 amp is separate room. Owners trying to get a temp occupancy until remaining work is completed. Owner will be on site . Phone #: ###-#### Inspection requested via web by Greg Traudt
No violation shall be retained, wall plates missing through out and opwn wires in room with wall removed.
210.8 All receptacles located within 6' of a sink shall have GFCI protection(owner stated sink will be removed or a GFCI will be put in place)
ELE18-00474 Electrical Rough-In2/6/20182/7/20182/7/2018 1:23:01 PMPPASS
We are requesting underground, wall rough-in and ceiling inspection for tomorrow morning. Our contact is Kory @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
U/G for floor boxes and misc walls opened up ok to cover. Only 3 walls opened in the North area.
ELE17-04333 Electrical Rough-In2/7/20182/7/20182/7/2018 12:50:41 PMPPASS
Okay to cover ceiling upstairs. Phone #: ###-#### Inspection requested via web by Bryan Atkins
Ceilings upstairs minus offfice ok to cover, Need to verify hook-up of blinds above ceiling to remove cords to feed motors and hard wire them
ELE18-00370 Permanent Service1/31/20182/7/20182/7/2018 11:22:17 AMAPASS
Any questions please call Louis at ###-#### or Jordan at ###-#### perm service inspection 200A upgrade Phone #: ###-#### Inspection requested via web by Louis Keller
p/s o/h rec ok
ELE18-00486 Final2/6/20182/7/20182/7/2018 10:08:20 AMAPASS
I included access info. with the project description. Phone #: ###-#### Inspection requested via web by Jonathan Poot
A/C install final ok
ELE17-03324 Electrical Rough-In2/6/20182/7/20182/7/2018 10:00:09 AMAPASS
3rd floor rooms Phone #: ###-#### Inspection requested via web by Tom Jenkins
3rd floor units ok to cover.
Warning given for staging sheetrock in units against walls pior to inspection
ELE18-00475 Electrical Rough-In2/6/20182/7/20182/7/2018 9:10:05 AMAPASS
we are requesting a rough-in inspection for the new gate for tomorrow morning. Our contact is Bryant @ ###-####. Thank you,
Phone #: ###-#### Inspection requested via web by Clint Tate
U/G for gate ok to cover
ELE18-00426 Final2/6/20182/7/20182/7/2018 8:37:45 AMAPASS
Phone #: ###-#### Inspection requested via web by Tyler Ridley
Final ok
ELE18-00370 Permanent Service1/31/20182/7/20181/31/2018 9:00:00 AMPCANC
Any questions please call Louis @ ###-#### or Jordan @ ###-#### Perm service inspection for 200A Service Upgrade Phone #: ###-#### >> Inspection requested via web by Louis Keller Inspection cancelled from web by: Louis Keller