MEC17-05511
| DOC - Permit Expired | 2/7/2019 | 2/7/2019 | 2/7/2019 2:39:51 PM | P | PASS |
|
|
Permit is being expired do to no scheduled activity in the last 180 days. A new permit will need to pulled if further inspections are required.
|
MEC17-05486
| DOC - Permit Expired | 2/7/2019 | 2/7/2019 | 2/7/2019 2:36:53 PM | P | PASS |
|
|
Permit is being expired do to no scheduled activity in the last 180 days. A new permit will need to pulled if further inspections are required.
|
MEC17-05476
| DOC - Permit Expired | 2/7/2019 | 2/7/2019 | 2/7/2019 2:35:51 PM | P | PASS |
|
|
Permit is being expired do to no scheduled activity in the last 180 days. A new permit will need to pulled if further inspections are required.
|
MEC17-05475
| DOC - Permit Expired | 2/7/2019 | 2/7/2019 | 2/7/2019 2:35:09 PM | P | PASS |
|
|
Permit is being expired do to no scheduled activity in the last 180 days. A new permit will need to pulled if further inspections are required.
|
MEC17-05473
| DOC - Permit Expired | 2/7/2019 | 2/7/2019 | 2/7/2019 2:33:46 PM | P | PASS |
|
|
Permit is being expired do to no scheduled activity in the last 180 days. A new permit will need to pulled if further inspections are required.
|
MEC17-05438
| DOC - Permit Expired | 2/7/2019 | 2/7/2019 | 2/7/2019 2:32:11 PM | P | PASS |
|
|
Permit is being expired do to no scheduled activity in the last 180 days. A new permit will need to pulled if further inspections are required.
|
MEC18-02215
| Conference | 2/7/2019 | 2/7/2019 | 2/7/2019 10:59:17 AM | A | DONE |
|
|
Met onsite to discuss the existing class 1 hoods. The existing hoods are not being altered, and are being left as they were originally installed and approved for the previouse tenant. Because of this I agreed to let them remain as, but that they need to install stainless steel on all the wall sufaces within 18" of the hoods, and use noncombustable panels in the grid ceiling with in 18" of the hoods. I also advised that we will need an air balance report for the existing hoods using ther CFM's shown on the drawings
|
MEC18-01798
| Mec-Aging Inspection | 2/7/2019 | 2/7/2019 | 2/7/2019 7:47:50 AM | | PASS |
|
|
|
MEC18-01798
| DOC - Permit Finaled | 2/7/2019 | 2/7/2019 | 2/7/2019 7:47:43 AM | A | PASS |
|
|
|
MEC17-05415
| Conference | 2/7/2019 | 2/7/2019 | 2/7/2019 7:43:54 AM | A | PASS |
|
|
Permit is being expired do to no scheduled activity in the last 180 days. A new permit will need to pulled if further inspections are required.
|
MEC19-00209
| Rough-in | 2/5/2019 | 2/7/2019 | 2/5/2019 2:42:00 PM | A | CANC |
|
|
Please call Jason 30min in advance so he can meet you onsite: ###-####. Needs rough-in inspection for MAU. Phone #: ###-#### >> Inspection requested via web by Melissa Skinner Inspection cancelled from web by: Melissa Skinner
|