ELE19-04348
| Electrical Rough-In | 2/7/2020 | 2/7/2020 | 2/7/2020 2:47:37 PM | P | PASS |
|
|
bldg 12 ceiling drops...west end 6 units ok to cover
|
ELE19-04867
| Final | 2/7/2020 | 2/7/2020 | 2/7/2020 2:07:35 PM | P | PASS |
|
|
Danny Phone #: ###-####...needed corrections made...all on surface..GFCI protected...ok to final
|
ELE19-04661
| Final | 2/7/2020 | 2/7/2020 | 2/7/2020 1:28:18 PM | P | FAIL |
|
|
Lock box Access code 7777 Phone #: ###-#### Inspection requested via web by Hidajet Zahic... all recepticles serving kitchen countertops shall have GFCI protection...kitchen island
|
MIS20-00041
| ELE-Conference | 2/7/2020 | 2/7/2020 | 2/7/2020 1:16:00 PM | P | DONE |
|
|
no permit for basement remodel...spoke with homeowner...electrical work done with out permits...downstairs kitchen added, bedroom added, and bathroom added...walls and ceiling sheetrocked and finished...homeowner changed stories on who did the work-him, contractor, and finally a buddy...double fee put on address for future permits...given 5 days to start the process
|
ELE20-00334
| Final | 2/6/2020 | 2/7/2020 | 2/7/2020 12:45:12 PM | A | FAIL |
|
|
Please call Dan prior to arrival. Thank you! Phone #: ###-#### Inspection requested via web by Lynn Proctor... called contact number...left message 10:15 AM...no response or call back
|
ELE20-00457
| Temporary Service | 2/7/2020 | 2/7/2020 | 2/7/2020 11:11:53 AM | P | PASS |
|
|
If possible please do inspection around 2 or 3pm. Phone #: ###-#### Inspection requested via web by Todd Hall...t/s u/g ok to connect
|
ELE20-00290
| Final | 2/6/2020 | 2/7/2020 | 2/7/2020 10:00:11 AM | A | PASS |
|
|
Robert Phone #: ###-####...job complete...240V 15A circuit added with exterior disconnect..ok to final
|
ELE19-03970
| Final | 2/6/2020 | 2/7/2020 | 2/7/2020 9:34:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kim Stolworthy...ok to final
|
ELE19-04920
| Final | 2/6/2020 | 2/7/2020 | 2/7/2020 9:18:35 AM | A | FAIL |
|
|
Garage code 2468, thank you! Phone #: ###-#### Inspection requested via web by Darryn Coburn... 1) all bedrooms shall have AFCI protection
2) surface mount incandescent light shall be a minumum 12" from edge of shelf...mst closet
|
ELE19-01592
| Final | 2/6/2020 | 2/7/2020 | 2/7/2020 8:26:22 AM | A | PASS |
|
|
garage code is 9239 10-2 was the old well wire before moved to other side of wall Phone #: ###-#### Inspection requested via web by Kevin Heideman...ok to final
|
ELE19-04113
| Final | 2/5/2020 | 2/7/2020 | 2/6/2020 12:47:21 PM | A | PASS |
|
|
All issues fixed. Phone #: ###-#### Inspection requested via web by Dan Jennings
|