Inspections for the day of: Friday, February 7, 2020.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-00253 Final2/3/20202/7/20202/7/2020 2:36:21 PMPFAIL
Sarah Shifley will meet and can be there anytime after 12pm Phone #: ###-#### Inspection requested via web by Devry King
- A/C needs locking caps installed on service ports
- gas line at furnace needs sediment trap after shut of valve
- condensate pump needs safety wired
MEC19-05099 Final2/4/20202/7/20202/7/2020 2:35:11 PMPNR
Requesting a final for Friday the 7th. PM. Please call Robbie prior to arrival. ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator
- talking with Robbie condensate lines are not complete and air balances are not finished.
MEC19-04908 Final2/4/20202/7/20202/7/2020 2:34:48 PMPNR
Requesting a final for Friday the 7th pm, Please call Robbie prior to arrival ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator
- talking with Robbie condensate lines are not complete and air balances are not finished.
MEC20-00431 Final2/5/20202/7/20202/7/2020 2:17:13 PMPPASS
Please call prior to arrival Phone #: ###-#### Inspection requested via web by Jamee Shoecraft
- fireplace final ok
MEC20-00537 Final2/6/20202/7/20202/7/2020 1:47:53 PMPCANC
Please call Joey on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- Talked with Joey over the phone and range vent has not been completed yet but a gas line is ready. need to adjust permit to show gas pressure test and schedule
MEC20-00544 Final2/6/20202/7/20202/7/2020 1:17:28 PMPPASS
Please call Paul prior to arrival to ensure ready; ###-####. Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- furnace ac coil co ok
MEC20-00503 Final2/6/20202/7/20202/7/2020 10:56:33 AMAPASS
Phone #: ###-#### Inspection requested via web by Joey Hickman
- final ok
MEC20-00506 Final2/6/20202/7/20202/7/2020 10:04:48 AMAPASS
Homeowner Adelino Soto ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- furnace only co ok
MEC19-05655 Final2/6/20202/7/20202/7/2020 9:32:10 AMAPASS
Front door should be open Phone #: ###-#### Inspection requested via web by Shaun Bevan
- final ok
MEC19-05616 Final2/6/20202/7/20202/7/2020 9:22:22 AMAFAIL
Mechanical Gas Fireplace Final Inspection. Homeowner has manual. Please call Eric @ ###-#### before heading there. Phone #: ###-#### Inspection requested via web by Dan Otero
- fireplace final fail R/I was never passed before being covered up. Gas line done by others still needs a permit and gas pressure test
MEC20-00418 Rough-in2/6/20202/7/20202/7/2020 8:58:37 AMAFAIL
GARI ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza
- fireplace venting has roofing tar all over vertical pipe. Replace tar covered vent pipe with new.
MEC19-03260 Mec-Aging Inspection2/7/20202/7/20202/7/2020 8:27:52 AM FAIL
Permit has not been active since 7-25-19 when it was issued. Schedule inspection with owners if work is finished. Permit will expire at next mechanical aging inspection if not active.
MEC15-01675 Mec-Aging Inspection2/7/20202/7/20202/7/2020 8:26:33 AM PASS
WIP