ELE05-00402
| Temporary Service | 2/7/2005 | 2/8/2005 | 2/8/2005 12:00:00 AM | A | PASS |
|
|
darrell-- ###-#### t/s u'g n ok 2/8/2005 8:27:26 AM
|
ELE05-00403
| Temporary Service | 2/7/2005 | 2/8/2005 | 2/8/2005 12:00:00 AM | A | PASS |
|
|
###-#### darrell t/s u/g n ok 2/8/2005 8:39:29 AM
|
ELE05-00404
| Temporary Service | 2/7/2005 | 2/8/2005 | 2/8/2005 12:00:00 AM | A | PASS |
|
|
brandon ###-#### called contractor and told him he had to provide job id sticker. t/s o/h n ok 2/8/2005 9:33:36 AM
|
ELE04-02855
| Final | 2/7/2005 | 2/8/2005 | 2/8/2005 12:00:00 AM | P | PASS |
|
|
Bill; Phone #: ###-#### Internet Inspection Request from: Jan Rice talked to contractor and said he has to verify panel schedule. ok to final 2/8/2005 7:45:25 PM
|
ELE04-03006
| Electrical Rough-In | 2/8/2005 | 2/8/2005 | 2/8/2005 12:00:00 AM | P | CANC |
|
|
bernice; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles for parking lot lighting, done yesterday. 2/8/2005 2:30:56 PM
|
ELE04-00825
| Final | 2/8/2005 | 2/8/2005 | 2/8/2005 12:00:00 AM | P | PASS |
|
|
monte ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr to have put in ko closure for bkr in panel. ok to final 2/8/2005 12:36:18 PM
|
ELE05-00377
| Permanent Service | 2/8/2005 | 2/8/2005 | 2/8/2005 12:00:00 AM | P | FAIL |
|
|
chuck ###-#### 250.24(A) grounding electrode conductor to be on same bar as grounded conductor. called contr, left corr notice 2/8/2005 1:28:56 PM
|
ELE05-00415
| Permanent Service | 2/8/2005 | 2/8/2005 | 2/8/2005 12:00:00 AM | P | FAIL |
|
|
chuck --###-#### 250.24(A) grounding electrode conductor to be on same bar as grounded conductor. Called contr, left corr. notice. 2/8/2005 1:26:37 PM
|
ELE05-00017
| Final | 2/3/2005 | 2/8/2005 | 2/8/2005 12:00:00 AM | P | PASS |
|
|
We installed a new 60 amp 480 volt 3 phase circuit #25-27-29 from Panel H1, to a new fused disconnect on the north wall. Wired to a transformer from this disconnect, and from this transformer to a receptacle for their new machine.This is in the northwest building.THANKS!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final 2/9/2005 10:09:49 AM
|