Inspections for the day of: Tuesday, February 8, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00685 FIR-Aging Inspection2/8/20052/8/20052/8/2005 12:00:00 AM NR
Per Chris with SimplexGrinnell work is in progress. 2/8/2005 3:30:47 PM
BLD04-01737 FIRE-Final Inspection2/8/20052/8/20052/8/2005 12:00:00 AMAPASS
Life safety finaled 2/8/2005 8:44:57 AM
FIR04-00666 INSP-Sprinkler Rough-in/Hydro2/7/20052/8/20052/8/2005 12:00:00 AMAFAIL
Inspection was for tenting in the west wing. Tenting not adequately attached to structure. Needs reinspection 2/8/2005 10:30:13 AM
FIR04-00666 INSP-Sprinkler Rough-in/Hydro2/7/20052/8/20052/8/2005 12:00:00 AMAFAIL
Inspection was for tenting in the west wing. Tenting not adequately attached to structure. Needs reinspection 2/8/2005 10:30:13 AM
FIR05-00046 INSP-Sprinkler Rough-in2/7/20052/8/20052/8/2005 12:00:00 AMAPART
Sprinkler piping is ok to cover except for the three areas marked on the approved plans that need modifications. One overspaced pendant upfront and two pendants off of 1" outlet in the rear. 2/8/2005 10:27:29 AM
FIR04-00674 INSP-Sprinkler Rough-in/Hydro2/7/20052/8/20052/8/2005 12:00:00 AMAPART
Hydro test for the 6th floor failed. Hydro test for the 1st floor passed. 2/8/2005 12:38:31 PM
BLD04-00450 FIRE-Final Inspection2/8/20052/8/20052/8/2005 12:00:00 AMPPASS
Fire life safety finaled 2/8/2005 12:24:59 PM
BLD04-02788 FIRE-Final Inspection2/8/20052/8/20052/8/2005 12:00:00 AMPPASS
Fire life safety finaled 2/8/2005 12:25:08 PM
BLD04-02204 FIRE-Final Inspection2/8/20052/8/20052/8/2005 12:00:00 AMPFAIL
Provide correct remote annunciators for the duct smoke detectors and then test. Remove thumbturn from the main entry/exit. Keyed is ok. Provide approved hardware on all other doors as per review comments and drawings. Provide exit discharge lighting as per review comments. 2/8/2005 3:27:36 PM
BLD03-02995 FIRE-Final Inspection2/8/20052/8/20052/8/2005 12:00:00 AMPPASS
fire life safety finaled 2/8/2005 12:26:24 PM
FIR04-00666 INSP-Sprinkler Rough-in/Hydro2/8/20052/8/20052/8/2005 12:00:00 AMPCANC
A stop work order has been issued by the electrical inspector for all work at the job site. No inspection performed for the west wing tenting. 2/8/2005 3:36:26 PM
BLD04-02715 FIRE-Conference2/8/20052/8/20052/8/2005 12:00:00 AMPCANC
John; Phone #: ###-#### Internet Inspection Request from: Jan Rice
BLD04-02716 FIRE-Conference2/8/20052/8/20052/8/2005 12:00:00 AMPCANC
John; Phone #: ###-#### Internet Inspection Request from: Jan Rice