Inspections for the day of: Wednesday, February 8, 2006.
Number of inspections: 13
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02976 ELE-Request for Extension2/5/20072/6/2006 A 
pls extend
ELE05-01605 ELE-Aging Inspection2/8/20062/8/20062/10/2006 3:49:35 PM DONE
see final
ELE05-01656 ELE-Aging Inspection2/8/20062/8/20062/8/2006 4:10:18 PM DONE
see final
ELE06-00456 Electrical Rough-In2/8/20062/8/20062/8/2006 4:07:51 PMPPASS
ufer ground for the shell building call Dana ###-#### to meet you. ok to pour gec
ELE05-04112 Final2/8/20062/8/20062/8/2006 4:06:37 PMPFAIL
dan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice, 680.73 electrical equipment for tub shall be accessible without damaging building, 406.5 recpt faceplate shall seat against mounting surface (upper bath), 406.4 recpts shall be securely fastened in place(front room, north side), 110.3(B) listed equipment shall be installed in accordance with instructions(mbr closet light lens)
ELE06-00455 Electrical Rough-In2/8/20062/8/20062/8/2006 3:10:57 PMPPASS
James; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ric walls only ok
ELE06-00452 Rough-In Permanent Service2/8/20062/8/20062/8/2006 1:41:54 PMPPASS
Internet Inspection Request from: Rowdy Monroe called contr, left survey, 210.52(E) there shall be a recpt at front of dwelling, ric ok, p/s u/g n ok
ELE06-00381 Temporary Service2/7/20062/8/20062/8/2006 10:31:02 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Tina Payne met elect, left corr notice, 240.81 ckt breaker handle sjall be up in on position, 250.28(A) bonding jumper shall be done with green screw supplied, 110.3(B) equipment shall be installed with instructions included
ELE05-04648 Permanent Service2/7/20062/8/20062/8/2006 9:28:47 AMAPASS
please call 30 min prior to meet you//tracy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa talked to owner, told to provide abrasion protection for gec in sub-panel, and add bond bushing to service panel, put cover on subpanel prior to energizng panel. Told owner to call for ri before cover. p/s o/h n ok
ELE06-00437 Final2/7/20062/8/20062/8/2006 8:45:15 AMAPASS
Please call John before going to set up time to meet, so that he can show the work. ###-####; Phone #: ###-#### Internet Inspection Request from: Dana Moyer met contr, ok to final
ELE06-00353 Permanent Service2/7/20062/8/20062/8/2006 8:16:54 AMAPASS
Please Call Bobby Langner ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson called contr, corrections made, ric walls and insulated ceiling ok, p/s, exst meter pak, n, ok
ELE05-01575 Final2/8/20062/8/20062/8/2006 12:00:00 AMPPASS
ok to final
ELE05-01656 Final2/8/20062/8/20062/8/2006 12:00:00 AMPPASS
ok to final