Inspections for the day of: Friday, February 8, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03115 ELE-Aging Inspection2/8/20082/8/20082/11/2008 3:34:32 PM DONE
see final
ELE06-02960 ELE-Aging Inspection2/8/20082/8/20082/11/2008 3:16:41 PM DONE
called contractor, they will look at and call for final
ELE07-04127 Electrical Rough-In2/8/20082/8/20082/8/2008 4:10:37 PMPPASS
lynn Note: tile heat Phone #: ###-#### ok to cover floor heat
ELE06-03276 Final2/8/20082/8/20082/8/2008 2:59:32 PMPPASS
looked at sign, ok to final
ELE08-00013 Final2/8/20082/8/20082/8/2008 1:50:28 PMPFAIL
please final Phone #: ###-#### Internet Inspection Request from: gary batten called, left correction notice, NEC 348.30(A) fmc shall be securely fastened within 12" of cabinet, 210.12(B) bedrooms shall be protected by afci that supply all outlets (including lights)
ELE08-00302 Electrical Rough-In2/8/20082/8/20082/8/2008 12:46:53 PMPPART
jason Phone #: ###-#### ric ok except kitchen areas
ELE08-00208 Final2/7/20082/8/20082/8/2008 10:12:17 AMAPART
nigel Phone #: ###-#### checked generator for listing, signed structural card, will come for final after resistors are hooked up
ELE08-00226 Electrical Rough-In2/7/20082/8/20082/8/2008 9:42:22 AMAPASS
call Mike if needed for rough in inspection.
Permits 00255 and 00226 are right next to each other. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey walls only ok to cover
ELE08-00225 Electrical Rough-In2/7/20082/8/20082/8/2008 9:21:30 AMAPASS
call Mike if needed for rough in inspection. Phone #: ###-#### Internet Inspection Request from: Loren Ramsey changes, (low voltage) ok to cover
ELE08-00217 Electrical Rough-In2/8/20082/8/20082/8/2008 8:52:50 AMAPASS
This inspection is for a ceiling rough-in. Contact is Leo Lopez. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ok to cover sales area ceiling only
ELE08-00077 Final2/7/20082/8/20082/8/2008 8:27:08 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to final, signed structural card