Inspections for the day of: Friday, February 8, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-02296 FIRE-Final Inspection2/8/20082/8/20082/8/2008 4:41:06 PMPPASS
Life safety passed
FIR08-00057 INSP-Final Inspection2/7/20082/8/20082/8/2008 3:51:30 PMPCANC
Per rick there are phone line problems. Will be rescheduled.
FIR07-00921 FIR-Aging Inspection2/8/20082/8/20082/8/2008 3:40:45 PM NR
Per Larren this will be called in for monday.
BLD07-02145 FIRE-Final Inspection2/7/20082/8/20082/8/2008 3:32:12 PMAFAIL
The relocated fire hydrant to the southwest of the building does not meet the min. 18" from the ceter of the outlet to the ground requirement in NFPA 24 7.3.3. Also a new fire hydrant has been added roughly 30'-0" to the northeast of the building. This hydrant is not shown on the grading plans.
FIR07-00591 INSP-Final Inspection2/8/20082/8/20082/8/2008 3:09:51 PMPPASS
permit finaled
FIR07-01054 INSP-Sprinkler Rough-in2/8/20082/8/20082/8/2008 3:07:32 PMPFAIL
Additional upright sprinkler protection is required in the combustible concealed space due to the new duct work obstructing the spray of the existing upright fire sprinklers. Also the existing riser needs to have a current inspection.
FIR07-00579 INSP-Sprinkler Rough-in2/7/20082/8/20082/8/2008 3:05:20 PMAPASS
The inspection today was only for the two combustible pockets at the east entrance. Both of the pockets have been filled with insulation and can be covered.
BLD07-02282 FIRE-Final Inspection2/7/20082/8/20082/8/2008 1:22:50 PMAFAIL
One of the hvac units would not turn on so no fire alarm inspection could be performed. Exit signs and emergency lights tested ok. The thumbturns need to be removed from the front doors with stickers and indicators provided as well.
FIR07-00930 INSP-Final Inspection2/7/20082/8/20082/8/2008 1:21:22 PMAPASS
Permit finaled
BLD07-02296 FIRE-Final Inspection2/8/20082/8/20082/8/2008 1:20:48 PMPPASS
permit finaled
FIR07-00697 INSP-Supply line flush2/7/20082/8/20082/8/2008 9:49:33 AMACANC
Mike M is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
FIR07-00697 INSP-Sprinkler Rough-in2/7/20082/8/20082/8/2008 9:49:31 AMACANC
Mike M is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus