Inspections for the day of: Monday, February 8, 2010.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00046 INSP-Final Inspection2/8/20102/8/20102/8/2010 4:09:31 PMPFAIL
Change the text as discussed on the facp display to include the smoke detectors in the new bedrooms, provide sync on the horn as per nfpa 72 a6.8.6.5.3, battery and NAC circuits did not report a trouble at the facp from the NAC panel.
BLD09-00969 FIRE-Final Inspection2/8/20102/8/20102/8/2010 3:26:39 PMPFAIL
Provide the latest approved plans showing the door addition and repair the exit sign over the west facing exit doors.
BLD09-02154 FIRE-Final Inspection2/8/20102/8/20102/8/2010 3:25:36 PMPPASS
Life safety passed
FIR09-00731 INSP-Sprinkler Rough-in/Hydro2/8/20102/8/20102/8/2010 3:24:42 PMPPASS
The underground hydro test passed.
BLD09-02294 FIRE-Final Inspection2/5/20102/8/20102/8/2010 2:55:31 PMPPASS
Life safety passed
FIR09-00518 INSP-Final Inspection2/8/20102/8/20102/8/2010 2:43:48 PMPPASS
Permit finaled. The insulation has been provided where I spot checked the attic.
FIR09-00741 INSP-Final Inspection2/8/20102/8/20102/8/2010 12:17:32 PMPPASS
Permit finaled. The monitoring signals had to be modified while I was on site.
BLD09-01307 FIRE-Final Inspection2/5/20102/8/20102/8/2010 12:15:33 PMAPASS
Life safety passed
BLD09-00646 FIRE-Final Inspection2/5/20102/8/20102/8/2010 12:14:21 PMAPASS
This inspection did not require fire sign off since the scope of work had been changed. I did perform a conference with the contractor and the owner on requirements for the upcoming permit being issued for the tenant improvement. I noted missing sprinkler heads under a rear overhead door and a office in the warehouse area that will have a ceiling installed. Door hardware is missing or incorrect in several areas.
BLD09-01024 FIRE-Final Inspection2/5/20102/8/20102/8/2010 10:25:38 AMAPASS
Life safety passed
FIR09-00484 INSP-Final Inspection2/5/20102/8/20102/8/2010 10:25:01 AMAPASS
Permit finaled