BLD10-02444
| FIRE-Conference | 2/8/2011 | 2/8/2011 | 2/9/2011 5:17:51 PM | P | PART |
|
|
Regarding overhead fire sprinkler work.
|
BLD10-01564
| FIRE-Final Inspection | 2/8/2011 | 2/8/2011 | 2/9/2011 5:16:58 PM | P | PASS |
|
|
Site visit to confirm west side main entry exit sign and EM discharge light installation.
|
FIR11-00001
| INSP-Final Inspection | 2/8/2011 | 2/8/2011 | 2/8/2011 2:58:25 PM | P | PASS |
|
|
Hood suppression system operated correctly under test conditions. Inspection passed, corrections finished.
|
FIR08-00802
| FIR-Aging Inspection | 2/8/2011 | 2/8/2011 | 2/8/2011 2:27:42 PM | | NH |
|
|
Property is vacant- no tenant or occupancy.
|
FIR08-00767
| FIR-Aging Inspection | 2/8/2011 | 2/8/2011 | 2/8/2011 2:20:36 PM | | FAIL |
|
|
No call for inspection.
|
FIR10-00632
| INSP-Final Inspection | 2/7/2011 | 2/8/2011 | 2/8/2011 2:16:51 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR10-00540
| INSP-Sprinkler Rough-in | 2/7/2011 | 2/8/2011 | 2/8/2011 2:16:15 PM | A | PART |
|
|
Inspection for beam clamp retainers and seismic brace attatchments at the third floor pre-fireproof coatings okayed.
|
FIR10-00634
| INSP-Sprinkler Rough-in | 2/7/2011 | 2/8/2011 | 2/8/2011 2:13:34 PM | A | FAIL |
|
|
See plan set for annotations at locations in need of adjustment including coverage at concealed spaces, one area overspaced, matched temp. uprights, one existing head needs replaced, DP at the new freezer not yet installed, plan mod. pending for field changes per contractor.
|
MIS11-00026
| FIR-Final | 2/8/2011 | 2/8/2011 | 2/8/2011 2:08:36 PM | P | PASS |
|
|
Noted items include; remove dust covers at area smoke detectors, secure EOL notification appliance at ceiling junction box, provide approved hardware at the restroom door.
|
BLD11-00047
| FIRE-Final Inspection | 2/8/2011 | 2/8/2011 | 2/8/2011 12:00:00 AM | P | PASS |
|
|
Noted items include; remove dust covers at area smoke detectors, secure EOL notification appliance at ceiling junction box, provide approved hardware at the restroom door.
|