FIR12-00311
| FIR-Aging Inspection | 2/8/2013 | 2/8/2013 | 2/8/2013 5:01:53 PM | | DONE |
|
|
|
BLD13-00125
| FIRE-Final Inspection | 2/8/2013 | 2/8/2013 | 2/8/2013 5:00:14 PM | P | PASS |
|
|
Fire life safety inspection completed satisfactory.
|
FIR12-00679
| INSP-Sprinkler Rough-in/Hydro | 2/8/2013 | 2/8/2013 | 2/8/2013 4:57:37 PM | P | NH |
|
|
underground hydro - Don Phone #: ###-#### * No access to complete inspection.
|
BLD12-01850
| FIRE-Sprinkler Rough-in | 2/8/2013 | 2/8/2013 | 2/8/2013 4:55:47 PM | P | PART |
|
|
Overhead fire sprinkler work at the sheetrock ceilings is approved for cover. HVAC registers to stay a min. of 1' from pendent heads as discussed.
|
FIR13-00049
| INSP-Final Inspection | 2/7/2013 | 2/8/2013 | 2/8/2013 1:31:58 PM | A | PASS |
|
|
Scope of fire alarm work passed functional testing. Inspection passed, permit finaled.
|
FIR12-00108
| INSP-Sprinkler Rough-in | 2/7/2013 | 2/8/2013 | 2/8/2013 1:29:58 PM | A | FAIL |
|
|
Rough-in at the 3rd floor perimeter hard lid areas completed. Pendent heads in soffits at two locations including the NE and SE side as marked on approved plan set are overspaced- see dated annotations. Some ceilings okayed to cover- ref. plans, also noted possible shadowing at some areas.
|