Inspections for the day of: Wednesday, February 8, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03412 Final2/7/20172/8/20172/8/2017 2:58:14 PMPFAIL
9th floor Phone #: ###-#### Inspection requested via web by steve ragan
BCC 4-05-32- Code violations not to be retained. Repair existing MC and metal flex that had been installed above old grid without being supported.
330.30- Existing MC shall have supports not to exceed 6'.
348.30- Metal flex used to feed upper unit has broken interlock and shall have supports not to exceed 4 1/2'.
410.20- Luminaire outlet and cover shall provide room for conductors being installed. Canopy held down so would not pinch flexible cord of luminaire at mud ring. Canopy shall completely enclose outlet opening.
ELE16-03460 Final2/8/20172/8/20172/8/2017 1:37:07 PMPFAIL
garage code 1414. thank you Phone #: ###-#### Inspection requested via web by daniel bibikov
110.3- Outdoor receptacle outlets will not work. 1 front 1 rear.
200.7- White conductors used as ungrounded conductors shall be identified as other than white or neutral gray.
334.80- Max overcurrent device for 6-3 NM cable shall be sized to 60 degree column. 55 amp max 60 installed.
ELE17-00308 Temporary Service2/8/20172/8/20172/8/2017 10:27:51 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
t/s u/g n ok
ELE17-00295 Rough-In Permanent Service2/7/20172/8/20172/8/2017 9:50:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE17-00231 Rough-In Permanent Service2/7/20172/8/20172/8/2017 9:18:25 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Insulators started to insulate prior to inspection, told to leave. Last warning. Next job started early will be red tagged until all is removed.
Rough in ok cover p/s u/g n ok
ELE16-03412 Final2/7/20172/8/20172/7/2017 3:40:19 PMACANC
9th floor TI Phone #: ###-#### >> Inspection requested via web by steve ragan Inspection cancelled from web by: steve ragan