Inspections for the day of: Thursday, February 8, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-04129 Final2/8/20182/8/20182/8/2018 1:51:39 PMPPASS
Phone #: ###-#### Inspection requested via web by Patrick Paz final ok
ELE18-00514 Temporary Service2/8/20182/8/20182/8/2018 1:30:44 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE18-00468 Temporary Service2/8/20182/8/20182/8/2018 12:41:14 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE18-00467 Temporary Service2/8/20182/8/20182/8/2018 12:40:51 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE16-02746 Electrical Rough-In2/8/20182/8/20182/8/2018 12:13:16 PMPPASS
Rough electrical soffit 309-319 Phone #: ###-#### Inspection requested via web by Kenneth Chapman 309-320 Soffit only ok to cover
ELE18-00510 Conference2/8/20182/8/20182/8/2018 11:32:17 AMPDONE
Call Troy to meet at State street need to consult on what would be required so the mast can be raised Phone #: ###-#### Inspection requested via web by Don Conley Talked about raising height of mast. Informed Troy ID Power will not connect if weather head is 8ft above roof. Need to contact ID power to verify connect Height. Also need to supply intersystem bond and address any code violations in imediate area of panel.
ELE17-04268 Electrical Rough-In2/6/20182/8/20182/8/2018 11:02:37 AMAPASS
Pls contact Bryce (Foreman) @ ###-#### or George (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes listing inspection only ok
ELE18-00469 Electrical Rough-In2/7/20182/8/20182/8/2018 10:50:17 AMAPASS
under ground cover // Kevin Phone #: ###-#### underground from edge of pool to house only ok to cover
ELE17-03472 Final2/7/20182/8/20182/8/2018 10:35:31 AMAFAIL
Daniel Phone #: ###-#### 210.8A1 and A7. GFCI protection requiered in bathrooms and within 6ft of sinks. (Bad bathroom GFCI breaker, Laundry room recep and Down bar receps. 314.20. Boxes set back more than 1/4in shall have spark rings,(all receps maounted in tile back splash) 406.12 All dwelling receps shall be Tamper resistant. (GFCI receps in Kitchen)
ELE18-00300 Rough-In Permanent Service2/8/20182/8/20182/8/2018 9:50:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn rough in ok p/s u/g n ok
ELE18-00488 Rough-In Permanent Service2/6/20182/8/20182/8/2018 9:17:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok p/s u/g n ok
ELE13-01156 ELE-Aging Inspection2/8/20182/8/20182/8/2018 7:44:06 AM FAIL
Made several attempts to contact contractor. Made no progress. Still has not made attept to schedule final.