FIR13-00540
| FIR-Aging Inspection | 2/8/2018 | 2/8/2018 | 2/15/2018 1:44:54 PM | | DONE |
|
|
Permit has been expired due to work for FIR17-00259
|
BLD18-00115
| FIRE-Final Inspection | 2/8/2018 | 2/8/2018 | 2/8/2018 1:39:41 PM | P | PASS |
|
|
Life safety passed. Contractor agreed to change out the round knobs on the doors to lever (single action) type as per the Door Hardware Schedule on the approved plans. This needs to be done prior to a building inspection.
Santonio Phone #: ###-####
|
FIR17-00734
| INSP-Sprinkler Rough-in | 2/8/2018 | 2/8/2018 | 2/8/2018 1:38:03 PM | P | PART |
|
|
The sprinkler piping above the hard lids, as marked on the plans, is ok to cover. Plans however will need to be re-submitted due to pipe routing changes and pipe size changes. Also branchline restraints will possibly be needed as discussed where the 6" is exceeded for the hangers on the branchlines, also I need verification that nuts are not needed on the "side sammys" on the Z-pulins. Provide verification that the "Bottom Sammys" can be mounted on the bottom of the Z-purlins. If wood is going to be exposed at the top plate of the walls then upright sprinkler protection will be required.
Don Phone #: ###-####
|
FIR17-00734
| INSP-Supply line flush | 2/8/2018 | 2/8/2018 | 2/8/2018 12:33:09 PM | P | CANC |
|
|
Wrong permit number called in.
underground // Don Phone #: ###-####
|
BLD17-00017
| FIRE-Final Inspection | 2/7/2018 | 2/8/2018 | 2/8/2018 10:23:18 AM | A | PASS |
|
|
life safety passed
late am please// call 1/2 hr prior // Curt Phone #: ###-####
|
NAF17-00062
| INSP-Final | 2/7/2018 | 2/8/2018 | 2/8/2018 9:21:35 AM | A | FAIL |
|
|
Provide verification of the fire sprinkler system annual inspection, provide annual inspection for the fire extinguisher and lower to 48", repair the existing exit sign, provide sticker at the main exit as discussed.
Call prior to going Phone #: 4085291259 >> Inspection requested via mobile web by Travis Walker
|
BLD17-04332
| FIRE-Final Inspection | 2/7/2018 | 2/8/2018 | 2/8/2018 8:28:23 AM | A | PASS |
|
|
life safety passed
Tom Phone #: ###-####
|
FIR17-00735
| INSP-Final Inspection | 2/7/2018 | 2/8/2018 | 2/8/2018 8:28:02 AM | A | PASS |
|
|
Permit finaled
|
BLD17-03529
| FIRE-Final Inspection | 2/7/2018 | 2/8/2018 | 2/8/2018 7:56:34 AM | A | PART |
|
|
A temporary for life safety is ok per scott until a fire sprinkler permit is issued/passed for the require fire sprinkler modifications.
Devon Phone #: ###-####
|
BLD18-00114
| FIRE-Final Inspection | 2/7/2018 | 2/8/2018 | 2/8/2018 7:54:50 AM | A | PASS |
|
|
Life safety passed Troy Phone #: ###-####
|
FIR18-00096
| INSP-Final Inspection | 2/7/2018 | 2/8/2018 | 2/8/2018 7:27:43 AM | A | PASS |
|
|
Permit finaled.
ADAM CHITWOOD Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|