PLM05-00323
| Water and/or Sewer | 2/7/2005 | 2/9/2005 | 2/9/2005 12:00:00 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: george miller
|
PLM05-00242
| Final | 2/8/2005 | 2/9/2005 | 2/9/2005 12:00:00 AM | A | FAIL |
|
|
sandy or ray; Phone #: ###-#### Internet Inspection Request from: Barbara Moore remove water heater flex from reilef line, terminate at 90 deg 6" to 24" ag. 2/9/2005 8:53:42 AM
|
PLM05-00323
| Final | 2/9/2005 | 2/9/2005 | 2/9/2005 12:00:00 AM | A | PASS |
|
|
|
PLM05-00361
| Sprinkler (Final) | 2/9/2005 | 2/9/2005 | 2/9/2005 12:00:00 AM | A | PART |
|
|
tie in ok
|
PLM05-00360
| Water and/or Sewer | 2/9/2005 | 2/9/2005 | 2/9/2005 12:00:00 AM | P | PASS |
|
|
danny ###-#### final ok 2/9/2005 3:56:41 PM
|
PLM05-00313
| Plumbing Rough-in | 2/9/2005 | 2/9/2005 | 2/9/2005 12:00:00 AM | P | PASS |
|
|
Internet Inspection Request from: Kim Alderson ri ok 2/9/2005 2:04:30 PM
|
PLM05-00314
| Plumbing Rough-in | 2/9/2005 | 2/9/2005 | 2/9/2005 12:00:00 AM | P | PASS |
|
|
Internet Inspection Request from: Kim Alderson ri ok 2/9/2005 2:17:26 PM
|
PLM05-00326
| Plumbing Rough-in | 2/9/2005 | 2/9/2005 | 2/9/2005 12:00:00 AM | P | PASS |
|
|
Internet Inspection Request from: Kim Alderson ri ok 2/9/2005 1:42:43 PM
|
PLM05-00361
| Sprinkler (Final) | 2/9/2005 | 2/9/2005 | 2/9/2005 12:00:00 AM | P | NR |
|
|
nicole ###-#### just needs test 2/9/2005 3:29:59 PM
|
PLM04-03174
| Plumbing Rough-in | 2/9/2005 | 2/9/2005 | 2/9/2005 12:00:00 AM | P | FAIL |
|
|
Leo; Phone #: ###-#### Internet Inspection Request from: Jan Rice waste test failed, secure master shower valves, hang k.s. waste. roll master shower vent above flow line. cold water downstream of water softenor is undersized, 3" waste in the garage ceiling has been installed in a way that damages the floor joists, repair floor joists, reinstall in a way that doesn't damage floor joists, test and call for reinspection. 2/9/2005 3:17:45 PM
|