BLD08-00896
| FIRE-Final Inspection | 2/9/2009 | 2/9/2009 | 2/9/2009 4:39:04 PM | P | PASS |
|
|
Life safety passed
|
BLD08-01656
| FIRE-Final Inspection | 2/9/2009 | 2/9/2009 | 2/9/2009 4:37:33 PM | P | PART |
|
|
A temporary occupancy was given with sam rogers permission until the remain ceiling tile is installed and the exit discharge light outside of the kitchen door is installed and tested.
|
BLD07-00004
| FIRE-Final Inspection | 2/6/2009 | 2/9/2009 | 2/9/2009 4:35:49 PM | A | FAIL |
|
|
Provide missing fire hydrant per review note #1. Provide non-hardened locks per review note #4. Provide fire dept. signage per revierw note #5. Provide address on both sides of the building as discussed with a minumum of 4" contrasting color numbers. Provide suite numbers. Mount the fire extinguishers. Provide additional fire extinguisher for the vanilla finish tenant space. Repair and retest the exit discharge lights out of the warehouse area. Provide door to remain unlocked sticker at both of the keyed exits.
|
BLD08-01332
| FIRE-Final Inspection | 2/6/2009 | 2/9/2009 | 2/9/2009 4:35:07 PM | A | FAIL |
|
|
Provide missing fire hydrant per review note #1. Provide non-hardened locks per review note #4. Provide fire dept. signage per revierw note #5. Provide address on both sides of the building as discussed with a minumum of 4" contrasting color numbers. Provide suite numbers. Mount the fire extinguishers. Provide additional fire extinguisher for the vanilla finish tenant space. Repair and retest the exit discharge lights out of the warehouse area. Provide door to remain unlocked sticker at both of the keyed exits.
|
BLD07-00003
| FIRE-Final Inspection | 2/6/2009 | 2/9/2009 | 2/9/2009 4:34:29 PM | A | FAIL |
|
|
Provide missing fire hydrant per review note #1. Provide non-hardened locks per review note #4. Provide fire dept. signage per revierw note #5. Provide address on both sides of the building as discussed with a minumum of 4" contrasting color numbers. Provide suite numbers. Mount the fire extinguishers. Provide additional fire extinguisher for the vanilla finish tenant space. Repair and retest the exit discharge lights out of the warehouse area. Provide door to remain unlocked sticker at both of the keyed exits.
|
BLD06-03407
| FIRE-Final Inspection | 2/6/2009 | 2/9/2009 | 2/9/2009 4:33:42 PM | A | FAIL |
|
|
Provide missing fire hydrant per review note #1. Provide non-hardened locks per review note #4. Provide fire dept. signage per revierw note #5. Provide address on both sides of the building as discussed with a minumum of 4" contrasting color numbers. Provide suite numbers. Mount the fire extinguishers. Provide additional fire extinguisher for the vanilla finish tenant space. Repair and retest the exit discharge lights out of the warehouse area. Provide door to remain unlocked sticker at both of the keyed exits.
|
FIR08-00779
| INSP-Final Inspection | 2/9/2009 | 2/9/2009 | 2/9/2009 4:22:06 PM | P | PASS |
|
|
permit finaled
|
FIR08-00595
| INSP-Final Inspection | 2/9/2009 | 2/9/2009 | 2/9/2009 4:21:04 PM | P | PASS |
|
|
permit finaled
|
FIR08-00791
| INSP-Final Inspection | 2/9/2009 | 2/9/2009 | 2/9/2009 4:20:21 PM | P | PASS |
|
|
permit finaled
|
FIR08-00637
| INSP-Final Inspection | 2/6/2009 | 2/9/2009 | 2/9/2009 4:17:05 PM | P | PASS |
|
|
permit finaled
|
FIR09-00066
| INSP-Final Inspection | 2/9/2009 | 2/9/2009 | 2/9/2009 4:15:53 PM | P | PASS |
|
|
permit finaled
|
FIR08-00852
| INSP-Final Inspection | 2/6/2009 | 2/9/2009 | 2/9/2009 4:14:39 PM | A | PASS |
|
|
Both hood suppresson systems operated correctly.
|
FIR08-00736
| INSP-Final Inspection | 2/6/2009 | 2/9/2009 | 2/9/2009 4:13:28 PM | A | FAIL |
|
|
I witnessed the operation of a single door hold open which functioned correctly but no city approved plans were on site.
|
FIR09-00051
| INSP-Final Inspection | 2/3/2009 | 2/9/2009 | 2/9/2009 4:12:06 PM | A | CANC |
|
|
Cancel per alex Phone #: ###-####
|
FIR08-00831
| INSP-Sprinkler Rough-in/Hydro | 2/6/2009 | 2/9/2009 | 2/9/2009 4:02:18 PM | P | PASS |
|
|
The sprinkler piping located in the first floor B wing corridor above the sheet rock can be covered.
|
FIR09-00066
| INSP-Sprinkler Rough-in | 2/6/2009 | 2/9/2009 | 2/9/2009 12:00:00 AM | P | CANC |
|
|
kenny Phone #: ###-####
|