BLD09-00287
| FIRE-Conference | 2/9/2010 | 2/9/2010 | 2/9/2010 4:35:20 PM | A | DONE |
|
|
Completed on site review of city set plans and notes with contractor. Noted incorrect door hardware at the main entry/exit, five restrooms and the changing room. Missing one PFE at the second level, need to post fire access lane marking per sheet C1.1, post signage at the door to the FACP room, discussed exit signs, trade permit finals and two project related BLD permits.
|
FIR09-00354
| INSP-Final Inspection | 2/9/2010 | 2/9/2010 | 2/9/2010 4:21:54 PM | P | PASS |
|
|
Corrections per previous inspection repaired. Fire alarm testing passed, permit finaled.
|
FIR09-00409
| INSP-Final Inspection | 2/9/2010 | 2/9/2010 | 2/9/2010 4:21:06 PM | P | PASS |
|
|
Corrections finished, site testing passed, fire alarm permit final okayed. Noted 120V outside bell at the fire sprinkler riser did not operate during the waterflow test.
|
BLD10-00078
| FIRE-Final Inspection | 2/9/2010 | 2/9/2010 | 2/9/2010 4:17:50 PM | P | FAIL |
|
|
Correction items include door hardware at four locations ( two main entry/exits-STE 301 and 302, office in 301, and backward panic in hallway at 302), provide missing escutcheons for fire sprinkler heads at various locations, post suite address at 302, need stamped plans and notes on site at next visit, two sprinkler heads are overspaced off the new partition wall.
|
FIR09-00608
| INSP-Final Inspection | 2/9/2010 | 2/9/2010 | 2/9/2010 4:11:38 PM | P | PART |
|
|
Correction notice items verified for completion, remainder of alarm work passed site testing. Final pending offsite monitoring check via permit FIR09-00740. Contractor to provide missing signage at the door to the FACP room.
|
FIR10-00037
| INSP-Final Inspection | 2/8/2010 | 2/9/2010 | 2/9/2010 4:07:21 PM | A | PASS |
|
|
Scope of fire sprinkler permit work completed satisfactory. Noted new flow switch has been installed, however is not yet wired due to pending alarm permit for this aspect of the project.
|