Inspections for the day of: Tuesday, February 9, 2010.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-00173 FIRE-Final Inspection2/8/20102/9/20102/10/2010 7:15:05 AMPCANC
Cancelled due to time constraints but I spok to Lori at ###-#### on the phone and discussed getting the existing fire extinguisher tagged and providing the missing sticker over the main door. Inspection has been rescheduled for wednesday.
FIR09-00581 INSP-Supply line flush2/8/20102/9/20102/10/2010 7:13:24 AMPPASS
The underground supply line flush passed.
FIR09-00708 INSP-Sprinkler Rough-in2/8/20102/9/20102/10/2010 7:12:53 AMPPASS
The rough-in inspection for system 4 attic piping passed. Three baffles need installed as discussed. The 24 hour air test for system 4 was started at 2:00 with 52psi on the guage.
FIR09-00535 INSP-Final Inspection1/29/20102/9/20102/9/2010 3:18:19 PMPFAIL
Provide corrosion protection for the exterior sprinkler piping, provide ventilation per the review comments and nfpa 20, provide a floor drain per the review comments and nfpa 20, remove the old sprinkler piping, verify the nozzles are not plugged, provide complete testing for the entire scope of work (such as fire pump cert.), provide correct tamper switches (automatic resetting).
FIR09-00673 INSP-Final Inspection2/9/20102/9/20102/9/2010 3:12:48 PMPFAIL
The fire alarm permit could not be completed due to the project related fire sprinkler permit not being able to be completed. Pump running, phase reversal and loss of power have been verified. Rick replaced a module in the fire alarm panel while I was on site.
FIR09-00707 INSP-Sprinkler Rough-in2/8/20102/9/20102/9/2010 3:04:49 PMAPASS
See the city approved plans for locations where the sprinkler piping can be covered.
FIR09-00568 INSP-Final Inspection2/8/20102/9/20102/9/2010 10:50:06 AMPPASS
Permit finaled. The NetCon was a 5.
FIR09-00567 INSP-Final Inspection2/8/20102/9/20102/9/2010 10:49:13 AMPPASS
Permit finaled. The NetCon was a 5.
BLD09-00969 FIRE-Final Inspection2/9/20102/9/20102/9/2010 10:46:51 AMPPASS
life safety passed
BLD09-01564 FIRE-Final Inspection2/8/20102/9/20102/9/2010 9:38:09 AMAPASS
Life safety passed. The builder will provide the correct sticker at the main exit prior to the building inspection.
FIR09-00731 INSP-Supply line flush2/8/20102/9/20102/9/2010 8:14:41 AMAFAIL
The underground flush was not performed. Roy said they were not ready to go since he was missing the key.
FIR10-00046 INSP-Final Inspection2/8/20102/9/20102/8/2010 11:03:31 AMACANC
Tom Wahl Phone #: ###-#### Internet Inspection Request from: joe fink Inspection cancelled from web by: joe fink