FIR09-00175
| FIR-Aging Inspection | 2/9/2011 | 2/9/2011 | 2/10/2011 9:57:51 AM | | NR |
|
|
Per Bill these inspections are being addressed.
|
FIR10-00494
| INSP-Sprinkler Rough-in/Hydro | 2/9/2011 | 2/9/2011 | 2/9/2011 3:58:48 PM | P | PASS |
|
|
Hydro test passed. The 12 missing uprights have been added and the additional upright in the fire pump room has been provided. These items can be removed from the previous correction notice.
|
FIR10-00514
| INSP-Sprinkler Rough-in | 2/8/2011 | 2/9/2011 | 2/9/2011 3:53:17 PM | A | CANC |
|
|
Cancelled due to time constraints. Message was left on voice mail.
|
BLD09-00423
| FIRE-Final Inspection | 2/8/2011 | 2/9/2011 | 2/9/2011 3:46:15 PM | P | FAIL |
|
|
Remove the dead bolt and provide single action hardware on the exit door. Provide annual inspection for the fire extinguisher. Provide verification, through the mechanical inspector, that a type one hood is not going to be required over the grill.
|
BLD11-00253
| FIRE-Final Inspection | 2/8/2011 | 2/9/2011 | 2/9/2011 3:19:47 PM | A | PASS |
|
|
Life safety passed
|
FIR10-00300
| INSP-Final Inspection | 2/8/2011 | 2/9/2011 | 2/9/2011 2:50:49 PM | A | PASS |
|
|
Permit finaled.
|
BLD11-00106
| FIRE-Final Inspection | 2/7/2011 | 2/9/2011 | 2/9/2011 1:40:30 PM | A | FAIL |
|
|
Repair all of the exit signs and emergency lights. Provide annual inspection for all fo the fire extinguishers. Provide single action hardware on all doors including the south exit door and all fo the interior doors. Also a sprinkler head is located too close to a wall in the mechanical closet. This sprinkler work will require a separate permit.
|
FIR10-00236
| INSP-Final Inspection | 2/8/2011 | 2/9/2011 | 2/9/2011 11:49:54 AM | A | PASS |
|
|
Permit finaled. 200 degree pendants have been provided at the supply diffusers per Rick.
|
BLD10-01276
| FIRE-Final Inspection | 2/8/2011 | 2/9/2011 | 2/9/2011 11:47:39 AM | A | PASS |
|
|
Life safety passed.
|
BLD10-01285
| FIRE-Final Inspection | 2/8/2011 | 2/9/2011 | 2/9/2011 11:41:31 AM | A | PASS |
|
|
Life safety passed. The contractor is to have the address installed prior to the building inspection.
|
FIR10-00556
| INSP-Sprinkler Rough-in | 2/8/2011 | 2/9/2011 | 2/9/2011 9:10:15 AM | A | PASS |
|
|
See the city approved plans for locations where the sprinkler piping can be covered. It has been marked and initialed in red.
|
FIR10-00577
| INSP-Final Inspection | 1/28/2011 | 2/9/2011 | 2/9/2011 9:09:16 AM | A | FAIL |
|
|
The smoke detectors for door release shall be centered on the doorway. Also plans will either need to be resubmitted showing the 30cd strobe or as-builts with verification of EOL voltage drop.
|
FIR10-00521
| INSP-Final Inspection | 1/28/2011 | 2/9/2011 | 2/9/2011 9:07:21 AM | A | CANC |
|
|
The contractor did not have the city approved job site copy plans on site. No inspection was performed.
|
BLD10-02683
| FIRE-Final Inspection | 2/8/2011 | 2/9/2011 | 2/9/2011 8:40:37 AM | A | PASS |
|
|
Life safety passed
|
FIR11-00014
| INSP-Sprinkler Rough-in | 2/8/2011 | 2/9/2011 | 2/9/2011 12:00:00 AM | A | CANC |
|
|