Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00175 FIR-Aging Inspection2/9/20112/9/20112/10/2011 9:57:51 AM NR
Per Bill these inspections are being addressed.
FIR10-00494 INSP-Sprinkler Rough-in/Hydro2/9/20112/9/20112/9/2011 3:58:48 PMPPASS
Hydro test passed. The 12 missing uprights have been added and the additional upright in the fire pump room has been provided. These items can be removed from the previous correction notice.
FIR10-00514 INSP-Sprinkler Rough-in2/8/20112/9/20112/9/2011 3:53:17 PMACANC
Cancelled due to time constraints. Message was left on voice mail.
BLD09-00423 FIRE-Final Inspection2/8/20112/9/20112/9/2011 3:46:15 PMPFAIL
Remove the dead bolt and provide single action hardware on the exit door. Provide annual inspection for the fire extinguisher. Provide verification, through the mechanical inspector, that a type one hood is not going to be required over the grill.
BLD11-00253 FIRE-Final Inspection2/8/20112/9/20112/9/2011 3:19:47 PMAPASS
Life safety passed
FIR10-00300 INSP-Final Inspection2/8/20112/9/20112/9/2011 2:50:49 PMAPASS
Permit finaled.
BLD11-00106 FIRE-Final Inspection2/7/20112/9/20112/9/2011 1:40:30 PMAFAIL
Repair all of the exit signs and emergency lights. Provide annual inspection for all fo the fire extinguishers. Provide single action hardware on all doors including the south exit door and all fo the interior doors. Also a sprinkler head is located too close to a wall in the mechanical closet. This sprinkler work will require a separate permit.
FIR10-00236 INSP-Final Inspection2/8/20112/9/20112/9/2011 11:49:54 AMAPASS
Permit finaled. 200 degree pendants have been provided at the supply diffusers per Rick.
BLD10-01276 FIRE-Final Inspection2/8/20112/9/20112/9/2011 11:47:39 AMAPASS
Life safety passed.
BLD10-01285 FIRE-Final Inspection2/8/20112/9/20112/9/2011 11:41:31 AMAPASS
Life safety passed. The contractor is to have the address installed prior to the building inspection.
FIR10-00556 INSP-Sprinkler Rough-in2/8/20112/9/20112/9/2011 9:10:15 AMAPASS
See the city approved plans for locations where the sprinkler piping can be covered. It has been marked and initialed in red.
FIR10-00577 INSP-Final Inspection1/28/20112/9/20112/9/2011 9:09:16 AMAFAIL
The smoke detectors for door release shall be centered on the doorway. Also plans will either need to be resubmitted showing the 30cd strobe or as-builts with verification of EOL voltage drop.
FIR10-00521 INSP-Final Inspection1/28/20112/9/20112/9/2011 9:07:21 AMACANC
The contractor did not have the city approved job site copy plans on site. No inspection was performed.
BLD10-02683 FIRE-Final Inspection2/8/20112/9/20112/9/2011 8:40:37 AMAPASS
Life safety passed
FIR11-00014 INSP-Sprinkler Rough-in2/8/20112/9/20112/9/2011 12:00:00 AMACANC
bryan Phone #: ###-####