Inspections for the day of: Thursday, February 9, 2012.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00193 Electrical Rough-In2/9/20122/9/20122/9/2012 2:37:47 PMPPASS
lynn Phone #: ###-#### walls and hard lids ok cover
ELE12-00102 Electrical Rough-In2/8/20122/9/20122/9/2012 2:00:43 PMPPASS
Look at underground PVC, and ground grid at bulk NH3 project. Phone #: ###-#### >> Inspection requested via web by Steve Moss ok cover u/g
ELE12-00273 Electrical Rough-In2/9/20122/9/20122/9/2012 1:05:11 PMPFAIL
mike Phone #: ###-#### called, main n-s u/g only ok cover, need to see terminations prior to cover, left correction notice, BCC 4-05-33(A)(B) all equipment shall be listed by a nationally recognized testing laboratory, NEC 110.3 listed or labelled equipment shall be installed in accordance with included instructions, 500.4 shall supply area classification drawing
ELE12-00157 Final2/8/20122/9/20122/9/2012 12:20:20 PMPPASS
Please call ###-#### when you are headed to inspection. Thanks Richard Phone #: ###-#### >> Inspection requested via web by Richard Corn ok final
ELE12-00269 Permanent Service2/9/20122/9/20122/9/2012 10:06:25 AMAPASS
called, told contractor to add abrasion protection for gec, label panel, then call for final, p/s o/h rec ok
ELE12-00277 Electrical Rough-In2/8/20122/9/20122/9/2012 10:04:19 AMAPASS
Robert-In the back yard- ok to enter Phone #: ###-#### ri ok
ELE12-00277 Final2/9/20122/9/20122/9/2012 10:04:08 AMAPASS
Robert-In the back yard- ok to enter Phone #: ###-#### ok final
ELE12-00269 Final2/8/20122/9/20122/9/2012 8:59:01 AMACANC
Inspection to have Idaho Power reconnect. There is a key stashed to the left of the front door in the weatherproof outlet cover. Call with any questions. Thanks, Eric ###-#### Phone #: ###-#### >> Inspection requested via web by Eric Schroeder called, see p/s
ELE11-02250 Electrical Rough-In2/8/20122/9/20122/9/2012 8:28:09 AMAPASS
Contact: Mike Mulvahill Phone #: ###-#### >> Inspection requested via web by Deb Gooden c wing area per green cover sticker ok