Inspections for the day of: Thursday, February 9, 2012.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00022 INSP-Final Inspection2/2/20122/9/20122/10/2012 11:52:33 AMACANC
Ray McQueen Phone #: ###-#### >> Inspection requested via web by Diane Turner
FIR12-00009 INSP-Final Inspection2/9/20122/9/20122/9/2012 2:40:00 PMPFAIL
Could not finish all testing today. To complete I need testing of duct smoke detectors, EOL voltage verification and sync of horn/strobes and final paper work .
FIR11-00671 INSP-Final Inspection2/8/20122/9/20122/9/2012 2:37:48 PMAFAIL
Need verification of resubmittals and final paper work. Alarm testing is complete.
BLD11-02578 FIRE-Final Inspection2/8/20122/9/20122/9/2012 2:36:54 PMACANC
Cancelled due to time constraints and Micron facilities plan review
FIR12-00035 INSP-Final Inspection2/8/20122/9/20122/9/2012 2:34:53 PMAPASS
Permit finaled. The hood suppression system functioned correctly
FIR11-00666 INSP-Final Inspection2/2/20122/9/20122/9/2012 1:03:27 PMAPASS
permit finaled. The netcon was a 5
FIR11-00563 INSP-Sprinkler Rough-in/Hydro2/9/20122/9/20122/9/2012 12:07:27 PMAPASS
The fourth floor insulation has been repaired. The piping can be covered in areas as marked on the plans with todays date.
BLD11-02165 FIRE-Final Inspection2/8/20122/9/20122/9/2012 11:55:14 AMAPASS
life safety passed
BLD12-00132 FIRE-Final Inspection2/7/20122/9/20122/9/2012 10:29:09 AMAPASS
life safety passed
FIR11-00543 INSP-Sprinkler Rough-in2/8/20122/9/20122/9/2012 10:26:54 AMAPASS
UG supply and Remote FDC are ok to cover. The thrust blocks have not been poured against undisturbed soil but per the contractor the surrounding soil, when backfilled, will be compacted to 95%.
BLD11-02973 FIRE-Final Inspection2/8/20122/9/20122/9/2012 7:43:26 AMAPART
A temporary occupancy is being given with Romeo Gervais permission until the fire alarm system has been addressed.