ELE11-02123
| ELE-Aging Inspection | 2/9/2016 | 2/9/2016 | 2/9/2016 3:08:56 PM | | PASS |
|
|
Still under construction
|
ELE16-00372
| Rough-In Permanent Service | 2/8/2016 | 2/9/2016 | 2/9/2016 3:03:27 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
408.41- Each grounded conductor shall terminate in an individual terminal. Will check on final. Rough in ok cover p/s u/g n ok
|
ELE15-03067
| Final | 2/9/2016 | 2/9/2016 | 2/9/2016 2:25:13 PM | P | PASS |
|
|
Robert Phone #: ###-#### Final ok
|
ELE15-03067
| Electrical Rough-In | 2/9/2016 | 2/9/2016 | 2/9/2016 1:38:05 PM | P | PASS |
|
|
Robert Phone #: ###-#### Heat pump rough in ok cover
|
ELE16-00377
| Permanent Service | 2/9/2016 | 2/9/2016 | 2/9/2016 1:18:14 PM | P | PASS |
|
|
Steve Phone #: ###-#### p/s o/h rec ok
|
ELE16-00285
| Final | 2/9/2016 | 2/9/2016 | 2/9/2016 12:48:29 PM | A | FAIL |
|
|
please call 45 minutes prior to inspection Phone #: ###-#### Inspection requested via web by John Edwards Contractor unable to meet will recall. Need labels, 210.64- receptacle outlet shall be located with in 50' of new electrical service. Unable to verify classification around both and oven areas.
|
ELE16-00380
| Electrical Rough-In | 2/8/2016 | 2/9/2016 | 2/9/2016 11:50:00 AM | A | FAIL |
|
|
Casey will be available. Call if necessary
Phone #: ###-#### Inspection requested via web by John Harvey 110.12(A)- Unused openings shall be closed. 2" KO back of panel. 110.12(B)- Damaged equipment shall be replaced. Temp pole outlet. 110.14(A)- Current carrying conductors shall terminate 1 per lug unless listed. Neutrals in neutral bar. 210.4(B)- Multi wire branch circuits shall have handle ties for disconnecting means. 250.110- Metal outdoor light boxes shall be connected to equipment ground. 312.3- Panel shall be held out so not to be recessed more than 1/4" from finished surface. 314.17(B)- NM cable shall be protected by bushing when entering metal boxes. 314.17(C)- NM cable sheath shall enter boxes minimum of 1/4". Several locations. 408.7- Unused breaker spaces shall be closed in panel and temp pole. 590.6(B)- Temp power receptacles other than 120 volt shall have GFCI protection. 240 volt 50 amp temp pole. Empty boxes in M. bath and up bed.
|
ELE16-00287
| Electrical Rough-In | 2/9/2016 | 2/9/2016 | 2/9/2016 11:04:55 AM | A | PASS |
|
|
Code for entry is 2508 Phone #: ###-#### Inspection requested via web by kendall bender Just down from customer service. Walls only rough in ok cover
|
ELE16-00336
| Final | 2/8/2016 | 2/9/2016 | 2/9/2016 9:31:20 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Greg Thomas Needed conference and rough in inspection
|
ELE16-00336
| Electrical Rough-In | 2/9/2016 | 2/9/2016 | 2/9/2016 9:30:44 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Thomas Kitchen remodel, attic junction boxes covers on, Rough in ok cover
|
ELE16-00336
| Conference | 2/9/2016 | 2/9/2016 | 2/9/2016 9:29:47 AM | P | DONE |
|
|
Phone #: ###-#### Inspection requested via web by Greg Thomas Discussed inspection proceedures, and required receptacle to left of back door when changed.
|
ELE15-03732
| Final | 2/9/2016 | 2/9/2016 | 2/9/2016 9:06:47 AM | A | FAIL |
|
|
Please contact Gary ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson Unit 104 locked and storage after waiting for general to unlock. Recall
|
ELE15-03733
| Final | 2/9/2016 | 2/9/2016 | 2/9/2016 8:39:37 AM | A | FAIL |
|
|
Please contact Gary ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson Water dripping out of can in dining are and 103 locked after waited for units to be unlocked. missed 1
|
ELE15-04016
| Electrical Rough-In | 2/8/2016 | 2/9/2016 | 2/8/2016 1:04:36 PM | A | PASS |
|
|
Floor heat Phone #: ###-#### Inspection requested via web by mike brown Up kids bath floor heat rough in ok cover
|