Inspections for the day of: Tuesday, February 9, 2016.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-02123 ELE-Aging Inspection2/9/20162/9/20162/9/2016 3:08:56 PM PASS
Still under construction
ELE16-00372 Rough-In Permanent Service2/8/20162/9/20162/9/2016 3:03:27 PMPPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe

408.41- Each grounded conductor shall terminate in an individual terminal. Will check on final. Rough in ok cover p/s u/g n ok
ELE15-03067 Final2/9/20162/9/20162/9/2016 2:25:13 PMPPASS
Robert Phone #: ###-#### Final ok
ELE15-03067 Electrical Rough-In2/9/20162/9/20162/9/2016 1:38:05 PMPPASS
Robert Phone #: ###-#### Heat pump rough in ok cover
ELE16-00377 Permanent Service2/9/20162/9/20162/9/2016 1:18:14 PMPPASS
Steve Phone #: ###-#### p/s o/h rec ok
ELE16-00285 Final2/9/20162/9/20162/9/2016 12:48:29 PMAFAIL
please call 45 minutes prior to inspection Phone #: ###-#### Inspection requested via web by John Edwards
Contractor unable to meet will recall. Need labels, 210.64- receptacle outlet shall be located with in 50' of new electrical service. Unable to verify classification around both and oven areas.
ELE16-00380 Electrical Rough-In2/8/20162/9/20162/9/2016 11:50:00 AMAFAIL
Casey will be available. Call if necessary

Phone #: ###-#### Inspection requested via web by John Harvey
110.12(A)- Unused openings shall be closed. 2" KO back of panel.
110.12(B)- Damaged equipment shall be replaced. Temp pole outlet.
110.14(A)- Current carrying conductors shall terminate 1 per lug unless listed. Neutrals in neutral bar.
210.4(B)- Multi wire branch circuits shall have handle ties for disconnecting means.
250.110- Metal outdoor light boxes shall be connected to equipment ground.
312.3- Panel shall be held out so not to be recessed more than 1/4" from finished surface.
314.17(B)- NM cable shall be protected by bushing when entering metal boxes.
314.17(C)- NM cable sheath shall enter boxes minimum of 1/4". Several locations.
408.7- Unused breaker spaces shall be closed in panel and temp pole.
590.6(B)- Temp power receptacles other than 120 volt shall have GFCI protection. 240 volt 50 amp temp pole.
Empty boxes in M. bath and up bed.
ELE16-00287 Electrical Rough-In2/9/20162/9/20162/9/2016 11:04:55 AMAPASS
Code for entry is 2508 Phone #: ###-#### Inspection requested via web by kendall bender Just down from customer service. Walls only rough in ok cover
ELE16-00336 Final2/8/20162/9/20162/9/2016 9:31:20 AMACANC
Phone #: ###-#### Inspection requested via web by Greg Thomas Needed conference and rough in inspection
ELE16-00336 Electrical Rough-In2/9/20162/9/20162/9/2016 9:30:44 AMPPASS
Phone #: ###-#### Inspection requested via web by Greg Thomas Kitchen remodel, attic junction boxes covers on, Rough in ok cover
ELE16-00336 Conference2/9/20162/9/20162/9/2016 9:29:47 AMPDONE
Phone #: ###-#### Inspection requested via web by Greg Thomas
Discussed inspection proceedures, and required receptacle to left of back door when changed.
ELE15-03732 Final2/9/20162/9/20162/9/2016 9:06:47 AMAFAIL
Please contact Gary ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson
Unit 104 locked and storage after waiting for general to unlock. Recall
ELE15-03733 Final2/9/20162/9/20162/9/2016 8:39:37 AMAFAIL
Please contact Gary ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson
Water dripping out of can in dining are and 103 locked after waited for units to be unlocked. missed 1
ELE15-04016 Electrical Rough-In2/8/20162/9/20162/8/2016 1:04:36 PMAPASS
Floor heat Phone #: ###-#### Inspection requested via web by mike brown
Up kids bath floor heat rough in ok cover