ELE13-02096
| ELE-Aging Inspection | 2/9/2016 | 2/9/2016 | 2/9/2016 2:46:50 PM | | DONE |
|
|
Talk with brad and will look into getting it finaled
|
GCE15-00150
| GCE-Final | 2/9/2016 | 2/9/2016 | 2/9/2016 2:43:01 PM | P | PASS |
|
|
Darren ###-#### corrections fixed final ok
|
GCE15-00155
| GCE-Final | 2/9/2016 | 2/9/2016 | 2/9/2016 2:42:19 PM | P | PASS |
|
|
Darren ###-#### corrections fixed final ok
|
ELE15-03955
| Final | 2/9/2016 | 2/9/2016 | 2/9/2016 1:55:28 PM | P | PASS |
|
|
Someone should be there . Call if not Phone #: ###-#### Inspection requested via web by Brian Hughes master bed final ok
|
ELE15-03639
| Rough-In Permanent Service | 2/9/2016 | 2/9/2016 | 2/9/2016 1:41:06 PM | P | PASS |
|
|
rough-in ok cover p/s u/g n ok
|
ELE16-00389
| Electrical Rough-In | 2/9/2016 | 2/9/2016 | 2/9/2016 1:25:49 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brad Girard kitchen remodel ok cover
|
ELE15-03371
| Final | 2/8/2016 | 2/9/2016 | 2/9/2016 1:24:47 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Brandon Hillman 210.52 receptalces in a pantry with finished counter top shall have GFCI protection 110.7 trim receptacle in make vanity in bath 408.4 field indentification required(label arc fault breakers) 352.30 riser shall be supported 250.94 intersystem bond required
|
ELE16-00266
| Rough-In Permanent Service | 2/9/2016 | 2/9/2016 | 2/9/2016 12:57:09 PM | P | PASS |
|
|
rough-in ok p/s u/g n ok
|