FIR18-00018
| INSP-Final Inspection | 2/9/2018 | 2/9/2018 | 2/9/2018 4:08:53 PM | P | CANC |
|
|
Wrong permit request generated, this inspection request is cancelled.
|
FIR17-00730
| INSP-Final Inspection | 2/9/2018 | 2/9/2018 | 2/9/2018 4:07:01 PM | P | PART |
|
|
Partial final fire sprinkler inspection complete, sprinkler heads need to be installed in verizon room located in the basement level, all other areas are complete for final fire sprinkler inspection.
|
FIR15-00088
| INSP-Conference | 2/8/2018 | 2/9/2018 | 2/9/2018 3:46:43 PM | P | DONE |
|
|
Fire conferenc complete.
|
BLD18-00065
| FIRE-Final Inspection | 2/9/2018 | 2/9/2018 | 2/9/2018 2:27:27 PM | P | PART |
|
|
Fire sprinkler inspection complete for scope of work areas, fire alarm inspection partially complete, contractor is waiting for parts to shunt trip elevator, fire extinguishers are in place with current inspection tags in scope of work areas. Partial completion for life fire safety for TCO, elevator shunt will be tested when install is complete.
|
BLD17-03243
| FIRE-Final Inspection | 2/9/2018 | 2/9/2018 | 2/9/2018 2:27:12 PM | P | PART |
|
|
Fire sprinkler inspection complete for scope of work areas, fire alarm inspection partially complete, contractor is waiting for parts to shunt trip elevator, fire extinguishers are in place with current inspection tags in scope of work areas. Partial completion for life fire safety for TCO, elevator shunt will be tested when install is complete.
|
FIR16-00383
| INSP-Alarm Testing | 2/9/2018 | 2/9/2018 | 2/9/2018 2:17:55 PM | P | DONE |
|
|
Fire alarm testing for levels 3 and 4 complete.
|
FIR17-00224
| INSP-Sprinkler Rough-in | 2/9/2018 | 2/9/2018 | 2/9/2018 12:41:47 PM | P | PASS |
|
|
Rough in inspection for overhead fire sprinkler pipig complete, sway bracing on main in middle part of building exceeds length for piping installed, piping will need to upsized to be compliant. Verfication of sway brace repair will be made at final inspection.
|
FIR17-00224
| INSP-Sprinkler Rough-in/Hydro | 2/8/2018 | 2/9/2018 | 2/9/2018 12:39:37 PM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure observed at contractor provided gauge at riser location.
|
FIR18-00080
| INSP-Sprinkler Rough-in | 2/8/2018 | 2/9/2018 | 2/9/2018 12:20:20 PM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler located above hardlid in conference room complete, conference room hardlid approved for cover.
|
FIR18-00099
| INSP-Final Inspection | 2/8/2018 | 2/9/2018 | 2/9/2018 11:57:10 AM | A | PASS |
|
|
Final commercial hood fire suppression system inspection complete.
|
FIR18-00032
| INSP-Final Inspection | 2/9/2018 | 2/9/2018 | 2/9/2018 10:04:50 AM | A | PART |
|
|
Fire alarm notification complete, fire sprinkler riser monitoring complete, elevator recall complete, remaining item to test is the elevator shunt.
|
FIR18-00032
| INSP-Alarm Testing | 2/8/2018 | 2/9/2018 | 2/9/2018 10:03:18 AM | A | DONE |
|
|
FIre alarm testing complete.
|