Inspections for the day of: Monday, March 1, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00826 BLD-Aging Inspection3/1/20043/1/20043/1/2004 12:00:00 AM PASS
Talked to Jack and he will get with Allied General about getting the alarm permit finished 3/2/2004 3:01:54 PM
FIR03-00315 INSP-Final Inspection2/24/20043/1/20043/1/2004 12:00:00 AMAFAIL
cliff-- ###-#### need resubmittals as there are two SNAC panels instead of one - 4 NAC are one SNAC and NAC 7-8 are on the other; batteries on SNAC aren't supervised; speakers are T-tapped; need maps; spot checked several smokes but need to test for alarm; need to check FACP for troubles; strobe to be 95 cd instead of 75 in SW gallery (see plans); need to test smokes for alarms and tampers plus manaul pulls and duct detectors; detectors 52 -and 53 are actually 72 and 74 - update maps/plans(didn't show up on address list either 3/1/2004 6:09:07 PM
FIR03-00538 INSP-Final Inspection3/1/20043/1/20043/1/2004 12:00:00 AMPPART
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie overhead hydro okay only; need to test tampers/alarms/flow and forward flow BFP 3/1/2004 5:59:31 PM
FIR04-00073 INSP-Alarm Testing3/1/20043/1/20043/1/2004 12:00:00 AMPPASS
Cell ph. ###-#### I will meet you at Denver way. If you know a time call me. Thanks!; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino The alarms tested okay as installed per plans; there is no BLD permit for occupancy and the occupancy may have changed from original occupancy; address on building is 3000 and the address on the permit is 3176; exit signs not working and need battery back-up; extinguishers needed; 3/1/2004 6:02:37 PM
FIR03-00601 INSP-Sprinkler Rough-in/Hydro3/1/20043/1/20043/1/2004 12:00:00 AMPPART
Mike; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes overhead hydro okay 3/1/2004 4:45:39 PM
FIR03-00616 INSP-Sprinkler Rough-in/Hydro3/1/20043/1/20043/1/2004 12:00:00 AMPFAIL
Mike; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes hydro failed; will reschedule 3/1/2004 4:45:53 PM
FIR03-00239 INSP-Sprinkler Rough-in/Hydro3/1/20043/1/20043/1/2004 12:00:00 AMPPASS
UG hydro okay 3/1/2004 5:20:56 PM
FIR03-00495 INSP-Final Inspection3/1/20043/1/20043/1/2004 12:00:00 AMPPASS
UG hydro okay