Inspections for the day of: Tuesday, March 1, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00384 Temporary Service2/28/20053/1/20053/1/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/28/2005 at 11:31:24 AM. Contact: ###-####. t/s u/g n ok 3/1/2005 7:57:45 AM
ELE05-00640 Electrical Rough-In2/28/20053/1/20053/1/2005 12:00:00 AMAPASS
###-#### - jessie ric ok, for walls and clg, addition only. 3/1/2005 9:39:25 AM
ELE05-00631 Temporary Service2/28/20053/1/20053/1/2005 12:00:00 AMAPASS
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles correction made, t/s u/g n ok 3/1/2005 8:37:22 AM
ELE05-00299 Final3/1/20053/1/20053/1/2005 12:00:00 AMPCANC
Internet Inspection Request from: Bob Glenn called contr. Wet floors. Left message to recall for insp. 3/1/2005 2:45:13 PM
ELE05-00300 Final3/1/20053/1/20053/1/2005 12:00:00 AMPCANC
Internet Inspection Request from: Bob Glenn called contr, left message to call when floors allow access 3/1/2005 4:22:16 PM
ELE05-00647 Permanent Service3/1/20053/1/20053/1/2005 12:00:00 AMPPASS
mike-- ###-#### p/s u/g reconnect from fire ok 3/1/2005 11:58:01 AM
ELE05-00617 Permanent Service3/1/20053/1/20053/1/2005 12:00:00 AMPPASS
hailey; Phone #: ###-#### Internet Inspection Request from: Barbara Moore sticker affixed, p/s o/h n ok 3/1/2005 9:28:43 AM
ELE05-00655 Rough-In Permanent Service3/1/20053/1/20053/1/2005 12:00:00 AMPFAIL
chris ###-#### 314.17(C) nm cable shall be 1/4" inside box, 314.17(A) shall provide cable connector at boxes where 1/2" ko is used, 300.4(D) nm cable shall be 1 1/4" from the edge of framing members, 110.12(C) there shall be no broken boxes(broken out clamps), 314.20 boxes shall be flush with surface, framing shall not be torn out and wire left hanging. BCC job id sticker shall be posted., called contr, left corr notice 3/1/2005 12:54:55 PM
ELE05-00656 Rough-In Permanent Service3/1/20053/1/20053/1/2005 12:00:00 AMPFAIL
chris ###-#### 300.4(D) nm cable shall be 1 1/4" from sdge of framing member, 314.23(B)(1) boxes shall be fastened, 314.23(B)(2) metal braces shall be fastened, BCC job id sticker shall be posted 3/1/2005 1:29:49 PM