ELE05-00855
| Conference | 3/1/2006 | 3/1/2006 | 3/1/2006 4:22:54 PM | P | DONE |
|
|
Contact: Shane Korte - Parking equipment portion; Phone #: ###-#### Internet Inspection Request from: Deb McCoy talked about options to segregate class 2&3 wiring from class 1 at parking lot attendant booth
|
ELE05-04132
| Electrical Rough-In | 2/28/2006 | 3/1/2006 | 3/1/2006 3:53:01 PM | P | PASS |
|
|
Dan; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong changed some wall switches after project being on hold. ok to cover walls only
|
ELE06-00709
| Temporary Service | 2/28/2006 | 3/1/2006 | 3/1/2006 2:57:29 PM | A | FAIL |
|
|
###-#### - spencer called contr, left correction notice, 312.5 all conductors entering enclosures shall have abrasion protection,110.12(C) there shall be no broken parts i.e. lb cover, 50a recpt,panel cover hinge pin
|
ELE06-00036
| Final | 3/1/2006 | 3/1/2006 | 3/1/2006 2:17:45 PM | P | PASS |
|
|
Clyde; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr to tighten box for 1 recpt, ok to final, signed card
|
ELE06-00224
| Final | 2/28/2006 | 3/1/2006 | 3/1/2006 1:59:38 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams called contr about light, open box and 1 lv wire. ok to final, signed occ card
|
ELE06-00708
| Temporary Service | 2/28/2006 | 3/1/2006 | 3/1/2006 1:58:13 PM | P | PASS |
|
|
###-#### - spencer told contr to put in abrasion prot for gec, t/s u/g n ok
|
ELE05-04651
| Final | 2/28/2006 | 3/1/2006 | 3/1/2006 10:38:31 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 2/28/2006 at 12:25:26 PM. Contact: ###-####. do not cover ceiling, met elect, left correction notice to owner 725.8 cables shall be installed such that the building will not damage cable. Such cables shall be supported by straps or hangers or similar fittings designed and installed so as to not damage the cable. 800.24 communications cable shall be installed per 300.11 and not be supported by ceiling grid
|
ELE05-03886
| Electrical Rough-In | 2/28/2006 | 3/1/2006 | 3/1/2006 10:34:00 AM | A | PASS |
|
|
Ceiling inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to cover ceilings
|
ELE05-00855
| Electrical Rough-In | 2/28/2006 | 3/1/2006 | 3/1/2006 9:34:59 AM | A | PART |
|
|
CONTACT: LYLE DEAN - TEMPORARY FINAL FOR FLOORS 1,2 & 3 ; Phone #: ###-#### Internet Inspection Request from: Deb McCoy most corrections done, will fix some attendant items and call back to get t/o
|
ELE06-00703
| Rough-In Permanent Service | 2/28/2006 | 3/1/2006 | 3/1/2006 9:27:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/28/2006 at 3:50:32 PM. Contact: ###-####. corr made, ric ok p/s u/g n ok
|
ELE05-04404
| Final | 3/1/2006 | 3/1/2006 | 3/1/2006 12:00:00 AM | A | PASS |
|
|
ok to cover ceiling, ok to final, did not sign card till garage opens
|