Inspections for the day of: Wednesday, March 1, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00855 Conference3/1/20063/1/20063/1/2006 4:22:54 PMPDONE
Contact: Shane Korte - Parking equipment portion; Phone #: ###-#### Internet Inspection Request from: Deb McCoy talked about options to segregate class 2&3 wiring from class 1 at parking lot attendant booth
ELE05-04132 Electrical Rough-In2/28/20063/1/20063/1/2006 3:53:01 PMPPASS
Dan; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong changed some wall switches after project being on hold. ok to cover walls only
ELE06-00709 Temporary Service2/28/20063/1/20063/1/2006 2:57:29 PMAFAIL
###-#### - spencer called contr, left correction notice, 312.5 all conductors entering enclosures shall have abrasion protection,110.12(C) there shall be no broken parts i.e. lb cover, 50a recpt,panel cover hinge pin
ELE06-00036 Final3/1/20063/1/20063/1/2006 2:17:45 PMPPASS
Clyde; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr to tighten box for 1 recpt, ok to final, signed card
ELE06-00224 Final2/28/20063/1/20063/1/2006 1:59:38 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Jim Williams called contr about light, open box and 1 lv wire. ok to final, signed occ card
ELE06-00708 Temporary Service2/28/20063/1/20063/1/2006 1:58:13 PMPPASS
###-#### - spencer told contr to put in abrasion prot for gec, t/s u/g n ok
ELE05-04651 Final2/28/20063/1/20063/1/2006 10:38:31 AMAPART
Scheduled by a contractor via Hello! on 2/28/2006 at 12:25:26 PM. Contact: ###-####. do not cover ceiling, met elect, left correction notice to owner 725.8 cables shall be installed such that the building will not damage cable. Such cables shall be supported by straps or hangers or similar fittings designed and installed so as to not damage the cable. 800.24 communications cable shall be installed per 300.11 and not be supported by ceiling grid
ELE05-03886 Electrical Rough-In2/28/20063/1/20063/1/2006 10:34:00 AMAPASS
Ceiling inspection.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to cover ceilings
ELE05-00855 Electrical Rough-In2/28/20063/1/20063/1/2006 9:34:59 AMAPART
CONTACT: LYLE DEAN - TEMPORARY FINAL FOR FLOORS 1,2 & 3 ; Phone #: ###-#### Internet Inspection Request from: Deb McCoy most corrections done, will fix some attendant items and call back to get t/o
ELE06-00703 Rough-In Permanent Service2/28/20063/1/20063/1/2006 9:27:00 AMAPASS
Scheduled by a contractor via Hello! on 2/28/2006 at 3:50:32 PM. Contact: ###-####. corr made, ric ok p/s u/g n ok
ELE05-04404 Final3/1/20063/1/20063/1/2006 12:00:00 AMAPASS
ok to cover ceiling, ok to final, did not sign card till garage opens