Inspections for the day of: Wednesday, March 1, 2006.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-00489 FIRE-Final Inspection2/27/20063/1/20063/1/2006 6:24:49 PMPNR
Inspection to be rescheduled as work is not ready per contractor.
FIR05-00594 INSP-Sprinkler Rough-in/Hydro2/28/20063/1/20063/1/2006 4:07:59 PMAPART
Overhead rough-in is good for cover at the 2nd thru 6th floor core areas including restrooms, elevator lobby, janitors closets, tele rooms and electrical rooms, discussed inspection method for the common floor areas, also inspected corridors and adjacent meeting rooms at the 2nd floor.
FIR05-00465 INSP-Final Inspection3/1/20063/1/20063/1/2006 4:03:00 PMPPASS
Fire sprinkler passed final inspection, items on c/n are complete.
FIR06-00037 INSP-Sprinkler Rough-in/Hydro2/28/20063/1/20063/1/2006 2:14:41 PMAFAIL
Heads are overspaced at location adjacent to office wall and sales floor (exceeding 130ft/2), related demo permit FIR06-00010 must be called in for final, per plan review notes a plan re-submittal is required-see items #1thru 5, perform forward flow test for the backflow preventer (note: system riser modification may be required), system alarm and supervision must be tested and approved prior to final for this sprinkler permit.
BLD02-02178 FIRE-Final Inspection3/1/20063/1/20063/1/2006 10:26:01 AMAPART
Door closures have been adjusted, SD have been relocated in some units as required, exhaust fans have been connected to the light switch in the bathrooms, the smoke detectors in unit 422 have NOT been relocated to proper locations as required, no access to three units at this time due to tenant occupation.
BLD02-02177 FIRE-Final Inspection3/1/20063/1/20063/1/2006 10:19:58 AMAPART
Smoke detectors have been relocated as required, exhaust fans have been connected to the bathroom light fixtures, no access to some units as currently occupied, one SD at unit 504 needs to be repaired as it is not attatched to the ceiling.