ELE07-00608
| Temporary Service | 3/1/2007 | 3/1/2007 | 3/1/2007 3:00:01 PM | P | PASS |
|
|
Thanks Brad Phone #: ###-#### t/s u/g n ok
|
ELE07-00607
| Temporary Service | 3/1/2007 | 3/1/2007 | 3/1/2007 2:32:15 PM | P | PASS |
|
|
t/s u/g n ok
|
ELE07-00672
| Rough-In Permanent Service | 3/1/2007 | 3/1/2007 | 3/1/2007 1:44:53 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 3/1/2007 at 10:00:33 AM. Contact: ###-####. corrections made, ric core only ok, p/s u/g n ok
|
ELE07-00661
| Final | 3/1/2007 | 3/1/2007 | 3/1/2007 1:09:31 PM | P | PASS |
|
|
mitch; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
|
ELE06-03458
| Final | 3/1/2007 | 3/1/2007 | 3/1/2007 12:45:56 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/1/2007 at 8:18:17 AM. Contact: ###-####. called, left correction notice, nec 110.26(F)(2) there shall be no foreign piping systems in the zone described in 110.26(A), 406.4 receptacles shall be securely mounted in place, BCC address shall be attached to structure, all units shall be open for access, upper fire riser, 1 unit 2nd from left upper, 1 unit 2nd from right bottom, rest inspected
|
ELE07-00672
| Electrical Rough-In | 2/28/2007 | 3/1/2007 | 3/1/2007 10:01:34 AM | A | FAIL |
|
|
Heather; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called contr, no job id sticker, no address, no approved plans
|
ELE06-04726
| Electrical Rough-In | 2/28/2007 | 3/1/2007 | 3/1/2007 9:35:24 AM | A | PART |
|
|
please call Steve Ruter prior to inspect ###-#### Phone #: ###-#### talked to contr, left survey, nec 300.4(A)&(D) edge of bored holes and ent shall be 1 1/4" from edge of framing members, ric ok walls only except at panels
|
ELE06-04422
| Final | 2/28/2007 | 3/1/2007 | 3/1/2007 8:53:33 AM | A | PASS |
|
|
HZ call 30 min prior to inspection; Phone #: ###-#### Internet Inspection Request from: Stacie Backus corr made ok to final
|
ELE07-00497
| Rough-In Permanent Service | 2/28/2007 | 3/1/2007 | 3/1/2007 8:37:07 AM | A | PASS |
|
|
joe; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ric ok, p/s u/g n ok, met contr to see above ceilings
|