FIR06-00955
| INSP-Sprinkler Rough-in/Hydro | 3/1/2007 | 3/1/2007 | 3/2/2007 12:27:34 PM | P | PASS |
|
|
Above ground hydro test passed. This includes the anti-freeze loop.
|
BLD06-02534
| FIRE-Final Inspection | 3/1/2007 | 3/1/2007 | 3/2/2007 9:57:46 AM | P | FAIL |
|
|
Need fire alarm and fire sprinkler signed off first. No inspection performed.
|
BLD06-00212
| FIRE-Final Inspection | 3/1/2007 | 3/1/2007 | 3/2/2007 9:57:18 AM | P | FAIL |
|
|
Need fire alarm and fire sprinkler signed off first. No inspection performed.
|
BLD06-03452
| FIRE-Final Inspection | 3/1/2007 | 3/1/2007 | 3/1/2007 3:43:04 PM | P | FAIL |
|
|
Exit discharge lighting does not wor. Need updated map at the facp.
|
FIR06-00515
| INSP-Final Inspection | 2/28/2007 | 3/1/2007 | 3/1/2007 1:56:26 PM | P | CANC |
|
|
CONTACT: TODD Phone #: ###-#### Inspection cancelled from web by: Alicia Pauley
|
FIR07-00076
| INSP-Sprinkler Rough-in/Hydro | 2/28/2007 | 3/1/2007 | 3/1/2007 12:35:58 PM | P | PART |
|
|
Piping is ok to cover. One item that needs correct is the hanger rings that attach to the trapeze member are smaller in size than the pipe that they are supporting. These rings needs to be atleast 2 1/2" in size. This will be checked at the final.
|
FIR06-00466
| INSP-Final Inspection | 3/1/2007 | 3/1/2007 | 3/1/2007 12:15:35 PM | P | FAIL |
|
|
Items tested today include the phone lines, verified correct panel, interconnection of the six NAC panels to the FACP and tested all manual pull stations.
|
BLD05-03196
| FIRE-Final Inspection | 2/28/2007 | 3/1/2007 | 3/1/2007 11:37:19 AM | A | FAIL |
|
|
Provide signage at the gate as discussed.
|
FIR07-00099
| INSP-Final Inspection | 2/28/2007 | 3/1/2007 | 3/1/2007 10:57:22 AM | A | PASS |
|
|
Permit finaled
|
BLD05-01452
| FIRE-Final Inspection | 2/28/2007 | 3/1/2007 | 3/1/2007 10:54:28 AM | A | FAIL |
|
|
Provide city approved fire alarm plans that show all of the work being performed which includes the relocation of the smoke detectors from the deck to the ceilings, the relocation of fire smoke dampers and the relocation of magnetic door holders. Also emergency lighting is required in all paths of egress.
|
BLD06-02990
| FIRE-Final Inspection | 2/28/2007 | 3/1/2007 | 3/1/2007 9:36:06 AM | A | FAIL |
|
|
Provide approved door hardware on all doors. Remove dead bolts and mount and tag the fire extinguishers
|