Inspections for the day of: Thursday, March 1, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00955 INSP-Sprinkler Rough-in/Hydro3/1/20073/1/20073/2/2007 12:27:34 PMPPASS
Above ground hydro test passed. This includes the anti-freeze loop.
BLD06-02534 FIRE-Final Inspection3/1/20073/1/20073/2/2007 9:57:46 AMPFAIL
Need fire alarm and fire sprinkler signed off first. No inspection performed.
BLD06-00212 FIRE-Final Inspection3/1/20073/1/20073/2/2007 9:57:18 AMPFAIL
Need fire alarm and fire sprinkler signed off first. No inspection performed.
BLD06-03452 FIRE-Final Inspection3/1/20073/1/20073/1/2007 3:43:04 PMPFAIL
Exit discharge lighting does not wor. Need updated map at the facp.
FIR06-00515 INSP-Final Inspection2/28/20073/1/20073/1/2007 1:56:26 PMPCANC
CONTACT: TODD Phone #: ###-#### Inspection cancelled from web by: Alicia Pauley
FIR07-00076 INSP-Sprinkler Rough-in/Hydro2/28/20073/1/20073/1/2007 12:35:58 PMPPART
Piping is ok to cover. One item that needs correct is the hanger rings that attach to the trapeze member are smaller in size than the pipe that they are supporting. These rings needs to be atleast 2 1/2" in size. This will be checked at the final.
FIR06-00466 INSP-Final Inspection3/1/20073/1/20073/1/2007 12:15:35 PMPFAIL
Items tested today include the phone lines, verified correct panel, interconnection of the six NAC panels to the FACP and tested all manual pull stations.
BLD05-03196 FIRE-Final Inspection2/28/20073/1/20073/1/2007 11:37:19 AMAFAIL
Provide signage at the gate as discussed.
FIR07-00099 INSP-Final Inspection2/28/20073/1/20073/1/2007 10:57:22 AMAPASS
Permit finaled
BLD05-01452 FIRE-Final Inspection2/28/20073/1/20073/1/2007 10:54:28 AMAFAIL
Provide city approved fire alarm plans that show all of the work being performed which includes the relocation of the smoke detectors from the deck to the ceilings, the relocation of fire smoke dampers and the relocation of magnetic door holders. Also emergency lighting is required in all paths of egress.
BLD06-02990 FIRE-Final Inspection2/28/20073/1/20073/1/2007 9:36:06 AMAFAIL
Provide approved door hardware on all doors. Remove dead bolts and mount and tag the fire extinguishers