ELE10-00246
| Rough-In Permanent Service | 3/1/2010 | 3/1/2010 | 3/1/2010 3:57:23 PM | P | CANC |
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### see ri and p/s
|
ELE10-00246
| Electrical Rough-In | 3/1/2010 | 3/1/2010 | 3/1/2010 3:56:53 PM | P | FAIL |
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### called left correction notice, NEC 300.4(A)(1) edge of bored holes shall be 1 1/4" from edge of framing members, 314.17 conductors entering boxes shall be protected from abrasion-garage lights, 314.14 shall not exceed box fill for garage lights, NOTE: corrections shall be made within 5 working days or further action will be taken
|
ELE10-00246
| Permanent Service | 3/1/2010 | 3/1/2010 | 3/1/2010 3:52:17 PM | P | PASS |
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### p/s u/g n ok
|
ELE10-00185
| Final | 3/1/2010 | 3/1/2010 | 3/1/2010 3:51:04 PM | P | FAIL |
|
|
mike Phone #: ###-#### met contractor, correction notice,BCC4-05-33(A)(B) mixer and icemaker shall be listed by a nationally recognized testing laboratory, NEC 210.63 shall provide showroom receptacles, corrections shall be made within 5 working days or further action will be taken
|
ELE10-00386
| Conference | 3/1/2010 | 3/1/2010 | 3/1/2010 3:37:31 PM | P | DONE |
|
|
Steve Phone #: ###-#### talked about service and grounding, no esc this project
|
ELE10-00395
| Electrical Rough-In | 3/1/2010 | 3/1/2010 | 3/1/2010 2:49:18 PM | P | PASS |
|
|
Inspection requested from, web by: BARRY KENDALL Phone #: ###-#### corrections made, ri ok, no esc
|
ELE10-00395
| Final | 3/1/2010 | 3/1/2010 | 3/1/2010 2:49:01 PM | P | PASS |
|
|
Inspection requested from web by: BARRY KENDALL Phone #: ###-#### ok to final, no esc, signed card
|
ELE09-00026
| Final | 3/1/2010 | 3/1/2010 | 3/1/2010 2:43:50 PM | P | PASS |
|
|
Please call 30 minutes before so I can meet you there. Thanks Inspection requested from web by: Thomas Marshall Phone #: ###-#### ok to final, no esc this project
|
ELE10-00195
| Final | 3/1/2010 | 3/1/2010 | 3/1/2010 2:40:39 PM | P | FAIL |
|
|
corey Phone #: ###-#### ok to final, no esc this project called, left correction notice, BCC 4-05-33(A)(B) all equipment shall be listed by a nationally recognized testing laboratory, NOTE corrections shall be made within 10 working days or further action will be taken
|
ELE10-00330
| Rough-In Permanent Service | 2/26/2010 | 3/1/2010 | 3/1/2010 10:29:39 AM | A | PASS |
|
|
thank you!! Inspection requested from web by: Tracy Robertson Phone #: ###-#### ric ok, p/s u/g n ok
|
ELE10-00280
| Final | 2/26/2010 | 3/1/2010 | 3/1/2010 10:01:43 AM | A | FAIL |
|
|
Wayne Phone #: ###-#### met contractor, left correction notice, NEC 400.8(1) flexible cord shall not be used as a substitute for fixed wiring of structure, 410.62(C) shall permit cord connected if meetrs part (C)(1), NOTE corrections shall be made within 5 working days or further action will be taken, no esc this project
|
ELE10-00395
| Final | 2/27/2010 | 3/1/2010 | 3/1/2010 9:15:38 AM | A | FAIL |
|
|
Inspection requested from web by: BARRY KENDALL Phone #: ###-#### met contractor, left correction notice, NEC 110.12(A) shall close unused openings in box, 210.8(B)(2) all 125v receptacles in kitchen shall be gfci, 330.30(B) shall strap mc within 12" of box, 358.30(A) shall strap emt within 3' of box, 248.30(A) fmc shall be strapped within 12" of box, 300.15 shall provide box at termination of cable, BCC no violations shall be retained, NOTE- corrections shall be made within 5 working days or further action will be taken, NOTE: contractor shall call for ri for re-inspection, no esc this project
|
ELE10-00246
| Rough-In Permanent Service | 3/1/2010 | 3/1/2010 | 3/1/2010 8:39:31 AM | A | NR |
|
|
Inspection requested from web by: TOM BICANDI Phone #: ###-#### saw electrician, not done, see fee due
|