FIR11-00563
| INSP-Sprinkler Rough-in/Hydro | 3/1/2012 | 3/1/2012 | 3/2/2012 7:20:51 AM | P | NH |
|
|
please call when headded to the site . Phone #: ###-#### >> Inspection requested via web by Alicia Pauley
|
FIR11-00524
| INSP-Sprinkler Rough-in/Hydro | 2/28/2012 | 3/1/2012 | 3/2/2012 7:18:22 AM | P | PART |
|
|
Re-inspection for noted correction items at system 4 photo bay and link include: retainers at mains and branchlines secured; adjustments in pendent head locations at AMH track underway- overhead storage cubbies may also present obstruction issues when installed; seismic bracing completed; pendent heads at the link drop ceiling are matched with grid install to date. Plans will need revised to reflect field modifications at several areas.
|
FIR11-00448
| INSP-Sprinkler Rough-in/Hydro | 2/28/2012 | 3/1/2012 | 3/2/2012 6:55:51 AM | A | NR |
|
|
>> Inspection requested via web by Alicia Pauley *Contractor unable to locate plan set*
|
FIR11-00550
| INSP-Final Inspection | 2/27/2012 | 3/1/2012 | 3/2/2012 6:51:57 AM | P | PASS |
|
|
Balance of acceptance test items completed. Corrections finished. Fire alarm permit finaled.
|
FIR11-00556
| INSP-Final Inspection | 2/27/2012 | 3/1/2012 | 3/2/2012 6:49:49 AM | P | PASS |
|
|
Remainder of correction items verified for completion. Fire alarm permit finaled.
|
FIR12-00106
| INSP-Supply line flush | 3/1/2012 | 3/1/2012 | 3/2/2012 6:48:41 AM | P | PART |
|
|
UG fire supply line including the IBR to the contractor point of connection approved for bury.
|
FIR11-00631
| INSP-Final Inspection | 2/29/2012 | 3/1/2012 | 3/1/2012 1:58:46 PM | A | PASS |
|
|
Fire sprinkler permit finaled. Trip test and riser monitoring passed inspection.
|
FIR12-00011
| INSP-Final Inspection | 2/29/2012 | 3/1/2012 | 3/1/2012 1:56:25 PM | A | PASS |
|
|
Inspection passed. Noted delayed egress hardware is not yet installed- relays are in place- functionality cannot be verified at this time.
|
FIR11-00433
| INSP-Final Inspection | 2/29/2012 | 3/1/2012 | 3/1/2012 11:11:39 AM | A | PASS |
|
|
Adjustments finished. Fire alarm permit finaled.
|
BLD12-00230
| FIRE-Final Inspection | 2/17/2012 | 3/1/2012 | 3/1/2012 11:07:43 AM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD12-00245
| FIRE-Final Inspection | 2/29/2012 | 3/1/2012 | 3/1/2012 11:06:47 AM | A | FAIL |
|
|
Correction items include; provide approved hardware at the main exit door, remove manual thumbturn, post "door to remain..." signage, provide a current certification for the fire extinguisher.
|